INSTALLATION
INSTRUCTIONS
SERIES AH-WP INDOOR/OUTDOOR AUDIBLE HORN APPLIANCES
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s AH-WP Audible Horn Appliances are designed to provide a selectable continuous horn or code 3 tone when
connected directly to the Fire Alarm Control Panel (FACP), or provide a synchronized code 3 horn when used in conjunction
with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock’s Power Supplies. The AH-WP Appliances are UL Listed
under UL Standard 464 for Audible Signal Appliances. The AH-24WP is ULC Listed under Standard CAN/ULC-S525-99 for
Audible Signaling Appliances. They are listed for indoor and outdoor use and can be mounted to a 4” backbox (See Mounting
Options).
AH-WP Appliances can be field set to provide either High (HI) dBA, Medium (MED) dBA or Low (LO) dBA sound output.
All AH-WP models are designed for use with either filtered DC (VDC) or unfiltered Full-Wave-Rectified (FWR) input voltage.
All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP.
NOTE:
The code 3 horn incorporates the temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2
second on, 1-1/2 off and repeat) specified by ANSI/NFPA for standard emergency evacuation signaling.
The code 3 horn shall
be used only for fire evacuation signaling and not for any other purpose.
NOTE:
All
CAUTIONS
and
WARNINGS
are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: THE AH-WP APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.
FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS
COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE
PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 1: UL/ULC Listed Models and Ratings
Maximum RMS Current (AMPS)
DC
FWR
Model
Regulated
Voltage
(VDC/VRMS)
UL Voltage
Range
(VDC/VRMS)
ULC Voltage
Range
(VDC/VRMS)
Lo Med Hi Lo Med Hi
AH-24WP 24
16-33
20-31
0.021 0.043 0.080 0.041 0.051 0.090
AH-12WP 12
8-17.5
----- 0.058
0.108 0.192 0.059 0.109 0.209
Model AH-12WP is not ULC listed.
Table 1A: ULC Current Ratings 24VDC Models
Average Current (AMPS)
Model ULC
Voltage
(VDC/VRMS)
Lo Med Hi
20.0 .014
.020
.035
24.0 .017
.025
.050
AH-24
31.0 .021
.030
.065
Copyright 2005 Wheelock, Inc. All rights reserved.