Functions and control
1
4
Domestic air conditioner
7.Funcitions and control
7.1 Main functions and control specification
7.1.1 Automatic operation
When the running mode is turned to automation after starting the system, the system will first
determine the running mode according to the current room temperature and then will run according to
the determined mode. Tr in the following selection conditions means room temperature, Ts means
setting temperature, Tp means temperature of indoor coil pipe
Tr 23
Choose Cooling Mode
Tr
23
Choose Heating Mode
After turning to the automation mode, the running mode can be switched between cooling mode,
fan mode and heating mode according to the change of the indoor ambient temperature. But the
automatic conversion between cooling mode and heating mode must be conducted after 15 minutes.
7.1.2 Cooling operation mode
Temperature control range: 16
---30
Temperature difference: 1
* Control features: When Tr input airflow >Ts set temperature
, the compressor will be opened,
the indoor fan will operate at the set speed and the mode signal will be sent to the outdoor system.
When Tr input airflow
Ts set temperature
, the compressor will be opened, the indoor fan will
operate at the set speed and the mode signal will be sent to the outdoor system. The system will keep
the original status if Tr= Ts.
Airflow speed control: (temperature difference 1
)
Automatic: When Tr Ts+3
, high speed.
When Ts+1
Tr<Ts+3
, medium speed
When Tr<Ts+1
, low speed
When the sensor is off, low speed
When the airflow speed has no delay from the high to low switching, the speed should be delayed for
3 minutes (remain at high speed for 3 minutes.) before the next switch.
Manus: When the system is operating, you can set the high, medium or low speed manually. (When
the sensor is on or off, the system will change the speed 2 seconds after receiving the signal.)
*Airgate location control: the location for the airgate can be set according to your needs.
*Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or
dehumidifying). When the compressor works continuously for 1/6 minutes (adaptable in EEPROM)
and the temperature of the indoor coils has been below zero centigrade for 10 seconds, the
compressor will be stopped and the malfunction will be recorded in the malfunction list. The indoor
system will continue to run. When the temperature of the indoor coil is raised to 7
, the compressor
will be restarted again (the requirement of 3 minutes delay should be satisfied.)
* timing system on/off function.
* Dormant control function.
Summary of Contents for TERRA CH-S09FHCP
Page 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 ...
Page 14: ...Printed circuit board connector wiring diagram 12 Domestic air conditioner PCB ...
Page 49: ... ...
Page 50: ... ...
Page 51: ... ...
Page 52: ... ...
Page 53: ... ...
Page 54: ... ...
Page 55: ... ...
Page 56: ... ...
Page 57: ... ...