DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE
52
2.8 F1 Failure of Evaporator Temp. Sensor
2.9 F2 Temperature Sensor Error of Condenser
F3 Outdoor Temperature Sensor Error
F4 Discharge Temperature Sensor Error
yes
no
yes
no
yes
Temperature
sensor error
Is the plug of temperature sensor
connected correctly with the
socket of the mainboard?
Is the resistance value of the
temperature sensor within the normal
range?
Replace the mainboard of
indoor unit
Replace
temoperatire semspr
Confirm the direction of plug
and socket