DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE
51
2.6 E8 Overload of Indoor Fan
2.7 F0 Failure of Indoor Room Sensor at Air Intake
Failure of Indoor Room Sensor at
Air Intake
Remove the sensor to check if the
resistance value is ok?
check if the plug of the temperature sensor
is correctly connected with socket on the
main board?
Yes
replace main board of the
indoor unit
No
No
replace temperature sensor
check the directions of the
plug and socket
Yes
Overload of indoor fan
Is wire of indoor fan connected
rightly?
Connect the wire
rightly
Is setting of relay for indoor fan correct?
Set the correct rated value
Is the relay correct?
Replace the relay
Is the static pressure of the air duct
matched with the selected model?
Increase the static pressure of the air duct (turn
down the air valve)
Is the motor of the indoor unit
normal?
Replace the motor of the
indoor unit.
Remove error
Summary of Contents for FG20/C-M
Page 1: ...Duct Type Split Air Conditioner Service Manual ooper Hunter International Corporation USA...
Page 4: ...COMMERCIAL AIR CONDITIONER DUCT TYPE SPLIT AIR CONDITIONER 1 PRODUCT...
Page 16: ...DUCT TYPE SPLIT AIR CONDITIONER PRODUCT 13 5 2 Heat Pump...
Page 18: ...COMMERCIAL AIR CONDITIONER DUCT TYPE SPLIT AIR CONDITIONER 15 CONTROL...
Page 37: ...COMMERCIAL AIR CONDITIONER DUCT TYPE SPLIT AIR CONDITIONER 34 INSTALLATION...
Page 47: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 44 MAINTENANCE...
Page 58: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 55 FGR20 C M O FGR25 C M O...
Page 59: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 56 FG20 C M O F G25 C M O...
Page 60: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 57 FGR30 C M O...
Page 61: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 58 FG30 C M O FGR40 C M O...
Page 62: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 59 FG40 C M O...