COMMERCIAL AIR CONDITIONER
DUCT TYPE SPLIT AIR CONDITIONER
18
2.1 Cooling
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
cooling mode
compressor
outdoor fan
indoor fan
way
valve
time
turn off the
unit manually
turn on
the unit
When T
ambient
≥
T
setting
+
1 , the unit starts cooling. I
℃
n that case, the compressor, the outdoor
fan and the indoor fan will run. The outdoor fan will run for 15s before the compressor runs.
When T
ambient
≤
T
setting
—1 , the unit stops cooling.
℃
In that case, the compressor, the outdoor
fan will stop running while the indoor fan will run. The outdoor fan will stop after the compressor
stops for 15s.
When T
ambient
=
T
setting
, the compressor and the outdoor fan will remain the previous running
state and the indoor fan will run.
2.2 Dry Mode
compressor
outdoor fan
indoor fan
way
valve
OFF
ON
OFF
ON
OFF
OFF
ON
turn on
the unit
time
OFF
OFF
turn off the
unit manually
OFF
dry mode
Summary of Contents for FG20/C-M
Page 1: ...Duct Type Split Air Conditioner Service Manual ooper Hunter International Corporation USA...
Page 4: ...COMMERCIAL AIR CONDITIONER DUCT TYPE SPLIT AIR CONDITIONER 1 PRODUCT...
Page 16: ...DUCT TYPE SPLIT AIR CONDITIONER PRODUCT 13 5 2 Heat Pump...
Page 18: ...COMMERCIAL AIR CONDITIONER DUCT TYPE SPLIT AIR CONDITIONER 15 CONTROL...
Page 37: ...COMMERCIAL AIR CONDITIONER DUCT TYPE SPLIT AIR CONDITIONER 34 INSTALLATION...
Page 47: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 44 MAINTENANCE...
Page 58: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 55 FGR20 C M O FGR25 C M O...
Page 59: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 56 FG20 C M O F G25 C M O...
Page 60: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 57 FGR30 C M O...
Page 61: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 58 FG30 C M O FGR40 C M O...
Page 62: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 59 FG40 C M O...