4
1
Installation and Maintenance
Service Manual
Malfunction and mode display sheet
Malfunction name
Malfunction type
Double 8
Display of indicator
Operation
indicator
Cooling
indicator
Heating
indicator
Zero-cross detection circuit malfunction
Hardware
malfunction
U8
blinks 17 times
Malfunction protection of jumper cap
Hardware
malfunction
C5
blinks 15 times
No feedback of indoor motor
Hardware
malfunction
H6
blinks 11 times
Indoor ambient temperature sensor is
open/short- circuited
Hardware
malfunction
F1
blinks 1 times
Indoor evaporator temperature sensor is
open/short-circuited
Hardware
malfunction
F2
blinks 2 times
Liquid valve temperature sensor is
open/short-circuited
Hardware
malfunction
b5
blinks 19 times
Gas valve temperature sensor is
open/short-circuited
Hardware
malfunction
b7
blinks 22 times
Module temperature sensor is
open/short-circuited
Hardware
malfunction
P7
blinks 18 times
Outdoor ambient temperature sensor is
open/short- circuited
Hardware
malfunction
F3
blinks 3 times
Outdoor condenser inlet pipe temperature
sensor is open/short- circuited
Hardware
malfunction
A5
Outdoor condenser middle pipe
temperature sensor is open/short- circuited
Hardware
malfunction
F4
blinks 4 times
Outdoor condenser outlet pipe temperature
sensor is open/short- circuited
Hardware
malfunction
A7
/
/
/
Outdoor discharge temperature sensor is
open/short- circuited
Hardware
malfunction
F5
blinks 5 times
Communication malfunction of indoor
unit and outdoor unit
Hardware
malfunction
E6
blinks 6 times
Compressor phase current circuit
detection malfunction
Hardware
malfunction
U1
blinks 12 times
Compressor demagnetization protection
Hardware
malfunction
HE
blinks 14 times
DC busbar voltage drop malfunction
Hardware
malfunction
U3
blinks 20 times
Module temperature protection
Hardware
malfunction
P8
blinks 19 times
shortage of freon or blockage protection
for the system
Hardware
malfunction
F0
blinks 10 times
Capacitor charging malfunction
Hardware
malfunction
PU
blinks 17 times
High voltage protection for the system
Hardware
malfunction
E1
blinks 1 times
Low voltage protection for the system
Hardware
malfunction
E3
blinks 3 times
Compressor blockage
Hardware
malfunction
LE
/
/
/
Drive module reset
Hardware
malfunction
P0
/
/
/
Overspeed
Hardware
malfunction
LF
/
/
/
Drive board ambient temperature sensor
malfunction
Hardware
malfunction
PF
/
/
/
AC contactor protection
Hardware
malfunction
P9
/
/
/
9.2 Troubleshooting for Main Malfunction
(1) Troubleshooting for malfunction of temperature sensor
main check point:
●Whether the temperature sensor is broken or damaged;
●Whether the temperature sensor terminal is loosened or not connected;
●Whether the mainboard is damged;
Check flow chart:
Start the troubleshooting for
temperature sensor
Check whether the
temperature sensor and wiring terminal
is loosened or poorly connected?
Insert the temperature
sensor well
Is mafunction
eliminated?
Is mafunction eliminated?
Replace temperature with
the same mode
Check whether the
temperature sensor is normal by
refering the resistance value of
temperature sensor
Replace the controlle with
the same model
End
No
No
No
No
Yes
Yes
Yes
Yes
Summary of Contents for CH-S09FVX
Page 17: ...14 Technical Information Service Manual 18K 963 892 700 396 341 368 560 Unit mm...
Page 53: ...50 Installation and Maintenance Service Manual 10 2 Outdoor Unit 09K...
Page 55: ...52 Installation and Maintenance Service Manual 12K...
Page 57: ...54 Installation and Maintenance Service Manual 18K...