Chapter 7 Modbus mapping table
69
7.5.5 Set the master output function (Func: 03/06/16, RW: R/W)
NO(address)
Parameter
Description
Determination area
Unit
Factory
default
400201(00C8)
CH1
multi-segment
SV
Multi-segment
SV set
0: 1EA 1: 2EA 2: 4 EA
EA
0
400202(00C9)
CH1 Operation
volume
Operation
mode
select
0:Auto – operation volume
1:Manual – operating volume
-
Auto - MV
400203(00CA)
CH1 When
operating
manually,
Initial operation
When
operating
manually,
Initial
operation
0.0~100.0
(standard control mode)
-100.0 ~ 100.0
(Heating & Cooling control
mode)
%
0.0
400204(00CB)
CH1 Sensor error
The operation
volume when
the sensor is
in error
1. standard control mode
1) PID control : 0.0 ~ 100.0
2)ON/OFF control
:
0.0(OFF)/100.0(ON)
2. heating & cooling control
1) PID control : -100.0(cooling)
~ 100.0(heating)
2)ON/OFF
control:-100.0(cooling ON)
/0.0(OFF)/100.0(heating ON)
%
0.0
400205(00CC)
CH1 stop
operation volume
When the
control is
stopped, the
operation
volume
1. standard control mode
1) PID control : 0.0 ~ 100.0
2)ON/OFF control
:
0.0(OFF)/100.0(ON)
2. heating & cooling control
1) PID control: -100.0(cooling) ~
100.0(heating)
2)ON/OFF
control:-100.0(cooling ON)
/0.0(OFF)/100.0(heating ON)
%
0.0
400206(00CD)
-
-
-
-
-
400207(00CE)
~400250(00F9)
CH1 Reserved
401201(04B0)
~401250(04E1)
CH2 parameter - same as above CH1
402201(0898)
~402250(08C9)
CH3 parameter - same as above CH1