7392
ECP/RCP
S
YSTEM PROGRAMMER
I
NSTALLATION AND PROGRAMMING INSTRUCTIONS
Page 1: ...OES NOT COVER All damage resulting from faulty installation misuse negligence or abuse accidents acts of God or any other circumstance that is beyond Convectair s control This also applies to all repa...
Page 2: ...charging for 20 minutes the heater will be operating according to Monday s program at 00 00 AM until the day and time are reset 5 WARNINGS Manual override It s possible to override the heating status...
Page 3: ...ack Red Master heater Slave heater Slave heater Pilot wire Purple PILOT WIRE OK Prog PROG 1 2 3 4 5 6 7 There are 4 pre programmed groups of days 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 4 5 Note In these grou...
Page 4: ...day or exit by pressing Prog e Copying a program from another day b Customize a program Press Prog Select the day using and and press OK to validate Select the hour using et Press to choose between Co...
Page 5: ...day or exit by pressing Prog e Copying a program from another day b Customize a program Press Prog Select the day using and and press OK to validate Select the hour using et Press to choose between Co...
Page 6: ...ack Red Master heater Slave heater Slave heater Pilot wire Purple PILOT WIRE OK Prog PROG 1 2 3 4 5 6 7 There are 4 pre programmed groups of days 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 4 5 Note In these grou...
Page 7: ...charging for 20 minutes the heater will be operating according to Monday s program at 00 00 AM until the day and time are reset 5 WARNINGS Manual override It s possible to override the heating status...
Page 8: ...OES NOT COVER All damage resulting from faulty installation misuse negligence or abuse accidents acts of God or any other circumstance that is beyond Convectair s control This also applies to all repa...
Page 9: ...7392 ECP RCP SYSTEM PROGRAMMER INSTALLATION AND PROGRAMMING INSTRUCTIONS...
Page 10: ...A SETTING OF THE CLOCK B ASSIGNING PROGRAMS 5 OTHER FEATURES 8 A FROST PROTECTION MODE B MANUAL BYPASS C IN CASE OF A POWER FAILURE 6 LOCKING THE PROGRAMMER MODULE 9 7 PROGRAMMING EXAMPLE 9 A SETTING...
Page 11: ...e day and the present heating mode comfort economy or frost protection C to set time day and programming The 7392 ECP CASSETTE is designed to be inserted in the control panel of CONVECTAIR heaters mod...
Page 12: ...timetable for each day of the week indicates hour by hour 0 24h if we would prefer comfort setting or economy setting Seven pre selected programs reside in the CASSETTE Use them or create your own for...
Page 13: ...2 Place the transmitter CASSETTE in the receptacle of the unit assure that the mode selector is on programmer mode clock face Icon 3 Place all of the receiver CASSETTES in their appropriate units Fig...
Page 14: ...4 FIG 2A Installation Courant porteur Carrier current installation FIG 2B Installation avec appareils de salle de bain Installation including bathroom heaters...
Page 15: ...ECTAIR heaters equipped with a 7392 RCP CASSETTE for a maximum wire length of 90 to 100 feet 33 meters C Basic principle The Programmer system requires the installation of at least one CASSETTE 7392 E...
Page 16: ...92 ECP CASSETTE can control up to 20 Convectair units per Zone it is essential that the phases and loads be respected for instance 3750 W per 20 A circuit IMPORTANT If using a pilot wire communication...
Page 17: ...et the hour with or key and confirm with OK Set the minutes with or key and confirm with OK Set the day with or key and confirm with OK ex Monday 1 Tuesday 2 Sunday 7 B Assigning programs 7 pre select...
Page 18: ...ted by any one of the other ECP programer from any other zone Countdown starts immediatly and the original program will resume at midnight when the selected number of days is over To cancel the frost...
Page 19: ...The hours are flashing Using the or key set the hour display to 18 Confirm with OK and go to the minutes The minutes are flashing Using the or key set the minutes display to 18 Confirm with OK and go...
Page 20: ...e necessary to control a single Convectair heating unit A single 7392 ECP programmer CASSETTE transmitter can simply be installed in it s compartment see Fig 1A E Example of a programmable zone config...
Page 21: ...ettes are addressed only when the transmitter is on EMET mode 4 Repeat for each zone only when the transmitter for that zone is in EMET mode H Example of a configured zone The 7392 ECP CASSETTE Progra...
Page 22: ...PROGRAMMER MODULE 9 TROUBLE SHOOTING No display Check power supply to heater Make sure the PROGRAMMER MODULE is fully charged No signal Wrong signal Make sure that you have the same wire phase from o...
Page 23: ...the bathroom heater Why is it that the units with the pilot wire switch instantly while the units with the RCP s take longer If you are using a pilot wire your units shall switch to Hgel immediately...