PRIOR TO STARTING ENGINE
Prior to starting the engine, review the following settings.
Auto Start Configuration menu
Function
Description
Default Value
Auto Start Delay
Countdown period from remote start
signal to engine start
10 seconds
Preheat Time
Time to energize preheat circuit prior
to engine start
0 seconds
To enable preheat, an unused output relay must be assigned for the preheat function in the Output
Configuration menu (typically relay #1 or #3).
CAN Configuration menu
Function
Description
Default Value
Source Address
Match panel and ECU source address
(for proper communications from controller
over CAN bus)
44
TSC1 Address
Match panel and ECU TSC1 Address
(for proper throttle control)
234
Engine Address
Match ECU Engine Address
(
for proper communication to engine over
CAN bus
)
0
Engine Safety menu
Function
Description
Default Values
Overspeed
Alarm/Shutdown
The panel provides an overspeed
alarm/shutdown
ON
2010 rpm