CONTROLS, INCORPORATED
C O N T R O L S Y S T E M S & S O L U T I O N S
- 18 -
(7)
Auto Start Configuration
Auto Start Time Delay Selection (Default = 0:10)
Pre Heat Time Selection (Default = 0:00)
Crank Time Selection (Default = 0:10)
Crank Rest Time Selection ( Default = 0:10)
Warm Up Speed Selection (Default = 800 RPM)
Warm Up Time Selection (Default = 0:10)
Prime Speed Selection (Default = 800 RPM)
Prime Time Selection (Default = 0:00)
Cool Down Speed Selection (Default = 650 RPM)
Cool Down Time Selection (Default = 0:10)
Crank Cycles (Default = 5)
Fault Bypass Time Period Selection (Default = 0:10)
Crank Hold Delay Selection (Default = 0 TSec)
Crank Release Speed Selection (Default = 400 RPM)
Recharge Monitor On/Off (Default = Off)
Recharge Voltage Selection (Default = 119 Vx10)
Recharge Delay Selection (Default = 60 seconds)
Recharge Run Time Selection (Default = 15 minutes)
Next Recharge Time Interval Selection (Default = 45 minutes)
(8)
Auto Operation Settings
Start/Stop Input (Floats, Transducer) (Default = Floats)
Throttle Mode Selection (Default = Single Speed)
Operate Speed Selection (Default = 1800 RPM)
(9)
Transducer Configuration
Transducer Type (None/Floats, Level, Pressure) (Default = None/Floats)
Transducer Scale (4-20mA, 0-5VDC, Ratio Metric)
Min Transducer Reading (inches)
Max Transducer Reading (inches)
Current Level (current transducer reading display)
Zero Trim Calibration Setting
(10)
Maintenance Configuration
Service Interval Message Yes/No (Default = No)
Reset Interval Yes/No (Default = No)
Service Warning Hour Selection (Default = 0 hours)
Service Required Message Hour Selection (Default = 0 hours)
Next Service Warning Interval Selection (Default = 200 hours)
Next Service Required Interval Selection (Default = 250 hours)
1st Service Warning Interval Selection (Default = 75 hours)
1st Service Required Interval Selection (Default = 100 hours)