DIP SWITCHES SETTINGS
Set the DIP switches according to tables below. Power down and
power up again the actuator or act on the manual override handle
to be sure that settings will be recognized.
Factory settings
DIP
switch
OFF
ON
1
Direct Action
Reverse Action
2
Modulating Control (MOD) (Input between Y [+] and M [-])
3 point floating (INC) ( Y1 open-extend , Y2 close-retract
connected to M)
3
-
Selection of sequence mode, control range defined by DIP n.
5
4
Modulating Control 0-10Vdc
(DIP n. 2 OFF only)
Modulating Control 2-10Vdc
(DIP n. 2 OFF only)
5
Sequence Control 0-5Vdc with DIP n. 4 OFF only
Sequence Control 2-6Vdc with DIP n. 4 ON only
(DIP n. 3 ON only)
Sequence Control 5-10Vdc with DIP n. 4 OFF only
Sequence Control 6-10Vdc with DIP n. 4 ON only
(DIP n. 3 ON only)
6
Voltage Input Signal Vdc
(input between Y [+] and M [-])
Current Input Signal 4-20mA (input between Y [+] and M [-]).
In this case DIP n. 4 must be set to ON.
7
Automatic Calibration: the actuator updates the stroke range
if an unexpected mechanical stop is detected for at least 10s
Manual Calibration: the actuator calibration is started moving
the DIP from OFF to ON or vice versa. With DIP in ON in case
of extra stroke or if an unexpected endpoint is detected, the
actuator will never update the stroke