End Point Auxiliary Switches (with accessory DMVE)

End  point  switches  change  over  when  the  valve  is  fully  open  or 

closed. They are free contact with 24V AC/DC, 4A max voltage to 

terminals. 

End point switches can be utilized to indicate valve stroke end posi

-

tions and for relay control of additional plant equipment. When the 

actuators are controlled individually or in sequence, it is possible to 

use the end switches to toggle when the valve is fully open or fully 

closed. The auxiliary switch position according to control signal (Y) is 

shown in the table below.

Control signal (Y)

Relay 

KC1

Relay 

KC2

0-0,5Vdc

KC1 to K2

KC2 to K3

0,5-9,5Vdc

KC1 to K1

KC2 to K3

9,5-10Vdc

KC1 to K1

KC2 to K4

K1    K2  KC1

K1    K2  KC1

End point position

End point position

DMVE

RELE' DI CHIUSURA

RELE' DI APERTURA

K3    K4  KC2

Posizione di fine corsa

Posizione di fine corsa

K3    K4  KC2

OPENING RELAY

CLOSING RELAY

DMVE

TECHNICAL CHARACTERISTICS

DESCRIPTION

MVE204-65 

MVE204S-65

MVE206-65 

MVE206S-65

MVE210-65 

MVE210S-65

MVE215-65 

MVE215S-65

MVE222-65 

MVE222S-65

Supply voltage F N

230Vac ±10%, 50-60Hz

Power consumption (running)

10VA / 4,5W

13VA / 6W

18VA / 8W

21VA / 11W

25VA / 10W

Power consumption (holding)

8VA / 4W

11VA / 5W

11VA / 5W

13VA / 7W

10VA / 4W

Running time

Modulating

15 s (for valves with stroke from 5 to 15 mm)

60 s

(for valves with 

stroke from 5 to 60 

mm)

20 s (for valves with stroke from 15 to 25 mm)
30 s (for valves with stroke from 25 to 60 mm)

Increase/decrease

60 s

Stroke

5-60 mm (limited to 30 mm for MVE2xxS-65)

Force

400 N

600 N

1000 N

1500 N

2200 N

Duty cycle

max 50%/60 minutes

Analogue input Y M

voltage 0-10V - impedance > 100kΩ (range: 0-10Vdc, 2-10Vdc, 0-5/2-6Vdc, 5-10/6-10Vdc)

 

500 Ω (range 4-20mA)

Digital inputs Y1 Y2

connection of Y1, Y2 to M 

Output V+

voltage 16Vdc ± 0,5V, max load 25mA,

Output U

voltage 2-10Vdc (0-100%), max load 2mA

Room temperature

operation -10T55°C; storage -20T55°C

Room humidity

max 90% R.H.

Protection degree

IP65

Insulation class

Standard

Emission/Immunity EMC 2014/30/UE according to EN 61326-1:2013 standard

 

LVD 2014/35/UE according to EN61010-1:2010 standard

Material

housing: aluminium - cover: ABS plastic

Colour

aluminium / white

Weight [kg]

1.7 (MVE2xx-65); 1.6 (MVE2xxS-65)

Diagnostic

The actuator is provided with a self diagnostic algorithm able to de

-

tect faulty conditions:

• 

stroke calibration out of range 5-60mm;

• 

unexpected stall condition (e.g. valve stuck or extra stroke due 

to actuator link loose);

• 

voltage supply out of range. 

These faulty conditions are signalled via the GREEN and RED LED on 

the  electronic  board  blinking  accordingly  (see  Diagnostic  –  Alarm 

Function Table).

IP65

Protection against water and solid object IP65 is guaranteed by in

-

ternal seals, IP65 cable gland and the proper engineering of the en

-

closure.

One IP65 PG13,5 cable gland and one IP65 PG13,5 plug are supplied 

with the actuator.

1

st

 Issue rev. c

06/2020

DBL561e

Page 2

Summary of Contents for MVE2-65 Series

Page 1: ...odulating or proportional signal with field selectable range e g 0 10Vdc 2 10Vdc 0 5 2 6Vdc 5 10 6 10Vdc and 4 20mA Manual Override There is a manual operation handle on the actuator When it is low er...

Page 2: ...s for valves with stroke from 25 to 60 mm Increase decrease 60 s Stroke 5 60 mm limited to 30 mm for MVE2xxS 65 Force 400 N 600 N 1000 N 1500 N 2200 N Duty cycle max 50 60 minutes Analogue input Y M v...

Page 3: ...olli valves except for 2 3TGB F PN16 VSXT09PBP VSXT10PBP only with MVE204S 65 2 3TGB F PN16 Controlli valves with threaded M40 connections except for VSB VMB VSB F VMB F PN16 with AG51 VSB VMB VSB F V...

Page 4: ...1 F M N Neutral Modulating Control o 10 Vcc Modulating Control 0 10Vcc 230Vac Controller Command Command MVE M Y F N Neutral Note To avoid damages to electronic components caused by the PCB bending do...

Page 5: ...DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc w...

Page 6: ...nitial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and p...

Page 7: ...tor arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is...

Reviews: