OPERATION CONTINUED
TIME: 07:58:20 AM
DATE: 04/16/10
EXIT
PERIOD
MANUAL
ANNUAL
FACTORY
TEST DURATION : 0 m 30 s
ABORT
PRD : 30 DAYS
TIME & DATE : 10:00 PM 05/15/10
PERIODIC BATTERY TEST SETPOINTS
BATTERY TEST 00:00:07
DISABLED. PUSH TO ENABLE.
INTELLISTAT TS
TM
MONITOR OPERATION
PERIODIC BATTERY TESTING
Default customer password = 05151
SYSTEM NORMAL
TIME: 07:58:00 AM
DATE: 04/16/10
EXIT
PERIOD
MANUAL
ANNUAL
FACTORY
DISABLED. PUSH TO ENABLE.
TEST DURATION : 0 m 30 s
TEST
PRD : 30 DAYS
TIME & DATE : 10:00 PM 05/15/10
PERIODIC BATTERY TEST SETPOINTS
Push to enable the test.
Factory preset disabled.
The test will auto run
at the time and date
programmed for the
programmed duration.
The test period is factory
preset for 30 days. Factory
preset to the 15th of the
following month from date
of shipment at 10PM.
Time, Date and period are
user accessible.
Pushing the test button will invoke the test regardless if the enable/disabled button is enabled or not.
TIME: 07:58:17 AM
DATE: 04/16/10
EXIT
PERIOD
MANUAL
ANNUAL
FACTORY
TEST DURATION : 0 m 30 s
TESTING
PRD : 30 DAYS
TIME & DATE : 10:00 PM 05/15/10
PERIODIC BATTERY TEST SETPOINTS
BATTERY TEST 00:00:10
DISABLED. PUSH TO ENABLE.
The timer will count
down until the test is
complete and then
terminate the test
automatically. Test
results can be found
in the “TST LOG”
Menu.
While testing the
button will change
from “TESTING” to
“ABORT”. Press
the “ABORT” button
should you want
to terminate the
test immediately.
T h e b u t t o n w i l l
t h e n c h a n g e t o
“ABORTING” then
again back to the
original green “TEST”
button.
Test results can be found
in the “TST LOG” Menu.
If the “TST LOG” register
is full the system will
delete the oldest entry
to make room for the
new entry automatically.
Aborting the test will
result in a “Periodic Test
: Incomplete” entry in the
TST LOG.
Press the “TEST”
button to invoke a
battery test
(Duration
= 30 seconds). The
duration is preset at the
factory and is not user
accessible. Contact
the factory should the
duration time need to
be modified.
NOTE :
Invoking a test
by pressing the “TEST”
button will automatically
change the date and time
of the Periodic Test to the
date and time that the test
button is pushed. The
auto test will commence
exactly 30 days later on
the same date and time
the test button was initially
pushed (if enabled).