19
STEP 2 - SET MONITOR PARAMETERS
SYSTEM NORMAL
TIME: 07:58:17 AM
DATE: 03/31/10
X1
X2
LOW
BATTERY
CHARGE
LOAD %
MANUAL BYPASS
STATIC BYPASS
BATTERY
STATUS
INPUT
OUTPUT
PFC
LINK
INVERTER
PARAM
ALARMS
SETUP
TEST
ON/OFF
SYSTEM NORMAL
TIME: 07:58:17 AM
DATE: 03/31/10
EXIT
ENTER PASSWORD :
2
3
4
5
6
7
8
9
0
ENT
BS
1
MAIN
SYSTEM NORMAL
ALARM
1. From the home screen, select the “MAIN” button.
2. The main screen will appear, select “SETUP” button.
3. The “PASSWORD” screen will appear, enter
01955 as the password and then select “ENT”.
5. The “FACTORY SETPOINTS” screen will appear,
select the “VIN” box
.
WARNING - DO NOT CHANGE ANY OTHER
PARAMETERS.
SYSTEM NORMAL
TIME: 07:58:17 AM
DATE: 03/31/10
EXIT
FACTORY SETPOINTS
HIGH
LOW
MAIN
FACT
RATED VA : 10000
PASSWORD : 22222
VIN : 208
RATED WATTS : 10000
AH : 100
X1 : 120
X2 : 120
UNIT OPTIONS : 3
6. The data entry screen for “VIN” will appear, enter
the desired input voltage (208 or 240 ONLY) into
the data entry screen and select “ENT”.
WARNING - DO NOT CHANGE ANY OTHER
PARAMETERS.
4. The “ALARM SETPOINTS - HIGH” screen will
appear, select “FACT”.
SYSTEM NORMAL
TIME: 07:58:17 AM
DATE: 03/31/10
EXIT
HIGH
LOW
MAIN
FACT
ALARM SETPOINTS : HIGH
AC VOLTS X1-N : 132
AC VOLTS X2-N : 132
VA X1-N : 5000
VA X2-N : 5000
CHARGING DC AMPS : 12
SYSTEM NORMAL
TIME: 07:58:17 AM
DATE: 04/16/10
EXIT
SETPOINTS
RATED VIN ( 240 )
2
3
4
5
6
7
8
9
0
ENT
BS
1
7. The monitor is now set for the proper input voltage, select the “EXIT” key on each screen until you get all the
way back to the “MAIN” screen.
***** CAUTION *****
THE FOLLOWING PROCEDURE MUST BE FOLLOWED EXACTLY. DO NOT ALTER ANY OTHER
PARAMETERS. THE PASSWORD GIVEN ALLOWS YOU TO MODIFY ALL FACTORY SETTINGS AND
SHOULD BE KEPT FROM UNAUTHORIZED PERSONEL.