Web Server and Setup Pages
WebRelay Users Manual
send on command when input off (no off command)
-
When a voltage is removed from the
input, a command is sent to the remote WebRelay to set the relay state to
on
. When a voltage is
applied to the input, no commands are sent to the remote WebRelay.
send off command when input off (no on command)
-
When a voltage is removed from the
input, a command is sent to the remote WebRelay to set the relay state to
off
. When a voltage is
applied to the input, no commands are sent to the remote WebRelay.
send off command when input on (no on command)
-
When a voltage is applied to the input,
a command is sent to the remote WebRelay to set the relay state to
off
. When a voltage is
removed from the input, no commands are sent to the remote WebRelay.
send pulse command when input on
-
When a voltage is applied to the input, a command is
sent to the remote WebRelay to pulse the relay. When a voltage is removed from the input, no
commands are sent.
send pulse command when input off
-
When a voltage is removed the input, a command is
sent to the remote WebRelay to pulse the relay. When a voltage is applied to the input, no
commands are sent.
send pulse command when input changes
-
When a voltage is applied to the input or
removed from the input, a command is sent to the remote WebRelay to pulse the relay.
send toggle command when input on
-
When a voltage is applied to the input, a command is
sent to the remote WebRelay to toggle the relay (change the remote relay to the state opposite
of its current state). When a voltage is removed from the input, no commands are sent.
send toggle command when input off
-
When a voltage is removed the input, a command is
sent to the remote WebRelay to toggle the relay (change the remote relay to the state opposite
of its current state). When a voltage is applied to the input, no commands are sent.
send toggle command when input changes
-
When a voltage is applied to the input or
removed from the input, a command is sent to the remote WebRelay to toggle the relay (change
the remote relay to the state opposite of its current state).
remote command equals local relay
-
This option is used to “daisy-chain” WebRelay units. In
this mode, commands are sent to the remote WebRelay based upon the state of the local relay
and not the local input. When the local relay changes state to
on,
a command is sent to the
remote WebRelay to set the relay state to
on
. When the local relay changes state to
off
, a
command is sent to the remote WebRelay to set the relay state to
off
.
Remote Relay IP Address
When any option in the ‘Remote Relay Options’ setting is selected other than
no remote relay control
,
commands are sent over the IP network to this address as the control voltage input changes.
Remote TCP Port
When any option in the ‘Remote Relay Options’ setting is selected other than
no remote relay control
,
commands are sent over the IP network to this TCP port on the remote WebRelay as the control voltage
input changes.
Relay #
When any option in the ‘Remote Relay Options’ setting is selected other than
no remote relay control
,
commands are sent to the remote device with this relay offset. This option should ALWAYS be set to 0,
unless the remote device is something other than WebRelay. This is used when the remote device has
multiple relays. For example, the WebRelay-Quad has 4 relays. To send commands to third relay on a
WebRelay-Quad, this option would be set to 3. To send commands to the first relay on a WebRelay-
Quad, this option would be set to 1.
Page 46
Xytronix Research & Design, Inc.