9.9.4 Revision
Class: 1 (0x1)
Instance: 1 (0x1)
Attribute: 4 (0x4)
The revision code is the combination of the major and minor revision
codes, where the major revision code is the low byte, and the minor
revision code is the high byte.
Action
Major Revision
Minor Revision
Read
100
#11.29
#11.29 Mod 100
9.9.5 Status
Class: 1 (0x1)
Instance: 1 (0x1)
Attribute: 5 (0x5)
This attribute represents the current status of the entire device. Its value
changes as the state of the device changes.
b15 b14 b13 b12 b11
b10
b9
b8
Major
fault (U)
Major
fault (R)
Minor
fault (U)
Minor
fault (R)
b7 b6 b5 b4 B3
b2
b1 b0
Configured Owned
R - Recoverable fault
U - Unrecoverable fault
9.9.6 Serial
Number
Class: 1 (0x1)
Instance: 1 (0x1)
Attribute: 6 (0x6)
All Control Techniques DeviceNet interfaces have a unique serial
number stored in the non-volatile memory.
9.9.7 Product
Name
Class: 1 (0x1)
Instance: 1 (0x1)
Attribute: 7 (0x7)
The Unidrive DeviceNet interface will return the string “UD77” when this
attribute is read.