38 Issue
Number:
2
9.7.4
Extended Speed and Torque Control
Output Assembly Object 23
The scanner must be configured for 6 Tx bytes (or 3 Tx words) if this
output assembly object is selected.
Word Function
Word 0
Basic Control Word (See section 9.11)
Word 1
Speed Reference (See section 9.11.13)
Word 2
Torque Reference (See section 9.11.13)
The Extended Control Word uses a full 16-bit word, with the bits having
functions as shown below. Refer to section 9.11 for mapping details of
each function.
b15 b14 b13 B12 b11 b10
b9
b8
b7 b6 b5 b4 b3 b2 b1 b0
NetRef
NetCtrl
FaultRst
RunRev
RunFwd
9.7.5 Basic
Speed
Control
Input Assembly Object 70
The scanner must be configured for 4 Rx bytes (or 2 Rx words) if this
input assembly object is selected.
Word Function
Word 0
Basic Status Word (See below)
Word 1
SpeedActual (See section 9.12.4)
The Basic Status Word uses a full 16-bit word, with the bits having
functions as shown below. Refer to section 9.11 for mapping details of
each function.
b15 b14 b13 B12 b11 b10 b9
b8
b7 b6 b5 b4 b3 b2 b1 b0
Running
Fwd
Faulted