SCADAWave Ultra JR5O
14
Quick Start Guide - Ultra JR50 Ethernet Data Radio
Applies to models Jx900-xxxxx-xHx(CSA Marked)
This equipment is suitable for use in Class I, Division 2, Groups A, B, C & D Hazardous Locations
and ordinary locations only.
When marked “CL I, DIV 2, GRP A, B, C, D”, the transceiver has been Certified for use in these
hazardous locations by the Canadian Standards Association ( CSA ) International. CSA certification
is in accordance with CSA Standard C22.2 No. 213-M1987 and UL Standard 1604 subject to the
following conditions of approval:
1.The radio modem must be mounted in a suitable enclosure so that a tool is required to gain
access for disconnection of antenna, power and communication cables
2.The antenna, DC power and interface cables that leave the enclosure must be routed through
conduit or other means suitable for Class I, Division 2 wiring, in accordance with the electrical
codes. The enclosure and wiring are subject to investigation by the local Authority Having
Jurisdiction at the time of installation.
3. Installation, operation and maintenance of the radio modem should be in accordance with the
radio modem’s user manual and the national Electrical Codes.
4. Tampering or replacement with non-factory components may adversely affect the safe use of
the radio modem in hazardous locations and may void the approval
5. A power connector with locking screws as supplied by Control Microsystems MUST be used
WARNING EXPLOSION HAZARD
Do not connect or disconnect this equipment unless power has been removed or the area is
known to be nonhazardous.
Secure all external connections that mate to this equipment by using screws, threaded
connectors, latching connectors, or other means provided with this product
Sustitution of components may impair suitability for Class I, Division 2.
Important Notices for Class I, Division 2
Groups A, B, C & D Hazardous Locations