25
-
3.5.3
"MIN. CURRENT %" setting:
1.
Enables defining value for minimal current under which
power factor correction is not required, the value entered as
% of the maximum current at the secondary current
transformer.
2.
In order to change the Min. Current %, scroll to Min. Current
% line and press "Enter". Min. Current % screen appears.
3.
Use the buttons F3 & F4 to move the cursor, to set the value
use buttons F1 & F2, when finished click “ENTER”.
3.5.4
"MIN. VOLTAGE" setting:
1.
Enables defining voltage low limit value, under this value all
the capacitors will be disconnected.
2.
In order to change the Min. Voltage, scroll to Min. Voltage
line and press "Enter". The Min Voltage screen appears.
3.
Use the buttons F3 & F4 to move the cursor, to set the value
use buttons F1 & F2, when finished click “ENTER”.
3.5.5
"MAX. VOLTAGE" setting:
1.
Enables defining voltage high limit value, above this value all
the capacitors will be disconnected.
2.
In order to change the Max. Voltage, scroll to Max. Voltage
line and press "Enter". The Max Voltage screen appears.
3.
Use the buttons F3 & F4 to move the cursor, to set the value
use buttons F1 & F2, when finished click “ENTER”.