Continental Hydraulics Installation Manual
Page 28 of 33
CEM-AA-B
CHI 1020611 01/2016
Command
Parameters
Unit
Group
FUNCTION
MIN:I
X
MAX:I
X
TRIGGER X
i= A|B
x= 0… 6000
x= 5000… 10000
x= 0… 3000
-
0.01%
0.01%
0.01%
STD
AA
RA
The output signal is adapted to the valve by these commands. The output signal (the maximum
valve current) is defined by the
MAX:I
value. The overlap (dead band of the valve) is
compensated by the
MIN:I
value. The activation of the MIN function is set with the
TRIGGER
. No
output can occur when the command is below the TRIGGER point. The TRIGGER is used to
avoid unrequested activation caused by small variations of the input signal. When using this
module as part of a closed position loop the trigger value should be reduced.
MAX:A
MIN:A
MIN:B
MAX:B
Input
O
u
tp
u
t
TRIGGER