Continental Fireplaces CDIZC - N Installation And Operating Instructions Manual Download Page 26

26

W415-0224 / G / 02.28.11

SYMPTOM

PROBLEM

TEST SOLUTION

Pilot will not light.

No spark at pilot burner.

 

-

Check if pilot can be lit by a match.

 

-

Check that the wire is connected to the push button igniter.  

 

-

Check if the push button igniter needs tightening.

 

-

Replace the wire if the wire insulation is broken or frayed.

 

-

Replace the electrode if the ceramic insulator is cracked 
or broken.

 

-

Replace the push button ignitor

Out of propane gas.

 

-

Fill the tank.

Spark gap is incorrect.

 

-

Spark gap should be 0.150” to 0.175” (5/32” to 11/64” 
approx.) from the electrode tip and the pilot burner. To 
ensure proper electrode location, tighten securing nut 
(fi nger tight plus 1/4 turn).

No gas at the pilot burner.

 

-

Check that the manual valve is turned on.

 

-

Check the pilot orifi ce for blockage.

 

-

Replace the valve.

 

-

Call the gas distributor.

Flames are consistently 
too large or too small. 
Carboning occurs.

Unit is over-fi red or underfi red.

 

-

Check pressure readings: 

 

-

Inlet pressure can be checked by turning screw (A) 
counter-clockwise 2 or 3 turns and then placing pressure 
gauge tubing over the test point. Gauge should read 

7” (minimum 4.5”) water column for natural gas or 13” 
(minimum 11”) water column for propane. Check with 
main burner is operating on ‘HI’.

 

-

Outlet pressure can be checked the same as above 
using screw (B). Gauge should read 3.5” water column 
for natural gas or 10” water column for propane. Check 
that main burner is operating on ‘HI’.

 

-

AFTER TAKING PRESSURE READINGS, BE SURE TO 
TURN SCREWS CLOCKWISE FIRMLY TO RESEAL. 
DO NOT OVER  TORQUE.

 

-

Leak test with a soap and water solution.

Flames are very aggressive.

Door is ajar.

 

-

Ensure the mechanical means of securing the door is 
providing a tight seal.

Carbon is being 
deposited on glass, logs 
or combustion chamber 
surfaces.

Air shutter has become 
blocked.

 

-

Ensure air shutter opening is free of lint or other 
obstructions.

Flame is impinging on the logs 
or combustion chamber.

 

-

Check that the logs are correctly positioned.

 

-

Open air shutter to increase the primary air.

 

-

Check the input rate: check the manifold pressure and 
orifi ce size as specifi ed by the rating plate values.

 

-

Check that the door gasketing is not broken or missing 
and that the seal is tight.

 

-

Check that both vent liners are free of holes and well 
sealed at all joints.

 

-

Check that minimum rise per foot has been adhered to 
for any horizontal venting.

White / grey fi lm forms.

Sulphur from fuel is being 
deposited on glass, logs or 
combustion chamber surfaces.

 

-

Clean the glass with a recommended gas appliance 
glass cleaner. 

 

-

DO NOT CLEAN GLASS WHEN HOT.

 

-

If deposits are not cleaned off regularly, the glass may 
become  permanently marked.

Exhaust fumes smelled in 
room, headaches.

Appliance is spilling.

 

-

Ensure exhaust bracket gasket seal.

 

-

Check door seal and relief fl ap seal.

 

-

Check for chimney blockage.

 

-

Check that chimney is installed to building code.

 

-

Room is in negative pressure; increase fresh air supply.

 

-

Check cap gasket on the fl ue pipe assembly.

Remote wall switch is in 
’OFF’ position; main burner 
comes on when gas knob 
is turned to ‘ON’ position.

Wall switch is mounted upside down.

 

-

Reverse.

Remote wall switch is grounding.

 

-

Replace.

Remote wall switch wire is grounding.

 

-

Check for ground (short); repair ground or replace wire.

Faulty valve.

 

-

Replace.

42.3_2B

P

I

PILOT

N

O

L

O

T

H

I

L O

F

F O

A

B

PILOT 

BURNER

THERMOCOUPLE

THERMOPILE

Summary of Contents for CDIZC - N

Page 1: ...r gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the supplier This appliance may be installed as an OEM installation in man...

Page 2: ...REMOVAL AND INSTALLATION 13 4 3 LOG PLACEMENT 14 4 4 GLOWING EMBERS 14 4 5 LOGO PLACEMENT 15 4 6 ALUMINUM EXTRUSION TRIM KIT INSTALLATION 15 5 0 OPERATION 16 6 0 ADJUSTMENTS 17 6 1 PILOT BURNER ADJUST...

Page 3: ...IMNEY CONNECTION section Trim see ALUMINUM EXTRUSION TRIM KIT INSTALLATION section Door see DOOR REMOVAL AND INSTALLATION section Rating Plate see RATING PLATE INFORMATION section Logs see LOG PLACEME...

Page 4: ...tive that the control compartments burners and circulating blower and its passageway in the appliance and venting system are kept clean The appliance and its venting system should be inspected before...

Page 5: ...h the appliance is to be installed is HEIGHT 14 5 WIDTH 25 DEPTH 11 The minimum allowable chimney flue size is 6 round 2 2 MINIMUM OPENING 44 7 8 36 1 2 4 SIDED BACKER PLATE ALUMINUM TRIM 36 15 1 2 25...

Page 6: ...n where the vent will pass through the house without cutting a floor or roof joist If the appliance is installed directly on carpeting vinyl tile or other combustible material other than wood flooring...

Page 7: ...er Column When the appliance is installed at elevations above 4 500ft and in the absence of specific recommendations from the local authority having jurisdiction the certified high altitude input rati...

Page 8: ...IL AUCUN MATERIAU DEVANT ENTRER EN CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT ELECTRICAL RATING CLASS 115V 1 5AMP 60HZ THE APPLIANCE MUST BE VENTED USIN...

Page 9: ...NON COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM COMBUSTIBLES USE WOLF STEEL LTD SUPPORT RING ASSEMBLY W010 0370 OR EQUIVALENT NON COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARA...

Page 10: ...chimney with screws and plugs not supplied C INSIDE Attach and secure the flex liners to the vent connection assembly using the same procedure as before ensuring that the marked exhaust liner is attac...

Page 11: ...use open flame WARNING RISK OF FIRE EXPLOSION OR ASPHYXIATION ENSURE THERE ARE NO IGNITION SOURCES SUCH AS SPARKS OR OPEN FLAMES SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING...

Page 12: ...ANY NON COMBUSTIBLE MATERIALS SUCH AS BRICK MARBLE GRANITE ETC PROVIDED THAT THESE MATERIALS DO NOT GO BELOW THE SPECIFIED DIMENSION AS ILLUSTRATED DO NOT STRIKE SLAM OR SCRATCH GLASS DO NOT OPERATE A...

Page 13: ...ERIALS MUST NOT INTERFERE WITH AIR FLOW THROUGH AIR OPENINGS LOUVRES OPENINGS OPERATION OF LOUVRES OR DOORS OR ACCESS FOR SERVICE OBSERVE ALL CLEARANCES WHEN APPLYING COMBUSTIBLE MATERIALS BEFORE DOOR...

Page 14: ...heat activated curing process A Place the rear log 1 onto the two log supports and against the air intake pipe B Position logs 2 and 3 against the grate posts and line up the studs located on the burn...

Page 15: ...cluded with each kit If this appliance is being installed into an existing wood burning zero clearance fireplace then be aware of this precaution Any circulation air opening may be covered with noncom...

Page 16: ...ERATION FOR YOURSAFETY READBEFOREOPERATING POUR VOTRE SECURITE LIRE AVANT DE FAIRE FONCTIONNER WARNING IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY D...

Page 17: ...ADINGS TIGHTEN SCREWS FIRMLY TO SEAL DO NOT OVER TORQUE LEAK TEST 39 6 PILOT BURNER THERMOCOUPLE THERMOPILE P I L O T PILOT SCREW A B 6 2 VENTURI ADJUSTMENT This appliance has an air shutter that has...

Page 18: ...FLAME MUST ENVELOPE UPPER 3 8 TO 1 2 OF THERMOCOUPLE THERMOPILE 6 3 FLAME CHARACTERISTICS 6 4 RESTRICTING VERTICAL VENTS Some vent configurations may display a very active flame If this appearance is...

Page 19: ...nd bottom of the door is not broken or missing Replace if necessary 8 If for any reason the vent air intake system is disassembled re install and re seal per the instructions provided for the initial...

Page 20: ...the gasket holding the glass in place Careful not to break the glass GLASS GASKET DOOR FRAME GLASS RETAINER WARNING DO NOT USE SUBSTITUTE MATERIALS GLASS MAY BE HOT DO NOT TOUCH GLASS UNTIL COOLED CAR...

Page 21: ...k on Because the blower is thermally activated when turned on it will automatically start approximately 5 15 minutes after lighting the appliance and will run for approximately 30 45 minutes after the...

Page 22: ...T IS AN INTEGRAL SAFETY COMPONENT REPLACE ONLY WITH A FAST ACTING THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD WARNING 8 0 REPLACEMENTS COMPONENTS REF NO PART NO DESCRIPTION 1 W725 0039 NATURAL GAS VALVE 1...

Page 23: ...ON OFF REMOTE 33 F52 THERMOSTATIC REMOTE 34 GD 660 REMOTE WALL SWITCH WITH 20 WIRE 35 GI823KT DECORATIVE BRICK PANELS 36 W175 0162 CONVERSION KIT NG LP 36 W175 0192 CONVERSION KIT LP NG 37 GIZBP6 3 3...

Page 24: ...24 W415 0224 G 02 28 11 7 6 16 5 27 28 21 35 41 1 24 2 14 10 11 12 13 47 45 38 40 41 3...

Page 25: ...burning no gas to main burner gas knob is on HI wall switch thermostat is on Thermostat or switch is defective Connect a jumper wire across the wall switch terminals if main burner lights replace swi...

Page 26: ...ames are very aggressive Door is ajar Ensure the mechanical means of securing the door is providing a tight seal Carbon is being deposited on glass logs or combustion chamber surfaces Air shutter has...

Page 27: ...ftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which may or may not be caused by mechan...

Page 28: ...28 W415 0224 G 02 28 11 11 0 SERVICE HISTORY 43 1...

Reviews: