3. External Connection
CNT-3208M-PE
33
External Device Connection 2 -TTL level input-
Connecting the TTL level input
Use the TTL-compatible input to connect the board to the TTL-compatible output circuit of a rotary
encoder or linear scale. The maximum input frequency is 10 MHz.
For use in two-phase input mode, connect both of the phase-A and phase-B inputs. For use in single-
phase input mode, connect either of them. If phase-Z is not used, the input need not be connected.
Detailed description of TTL level input circuit
Figure 3.7. TTL level input circuit and its sample connection
Figure 3.8. Input signal
-
The connection cable length should be within 1.5 m.
-
To prevent noise from causing a malfunction, arrange the connection cable as away from any other
signal conductor or noise source as possible.
-
In the input pin+, TTL level input circuit is parallel-connected.
-
Please use the shielded cable to meet “CE EMC Directive”.
t
PWL
t
PWH : High-level count input pulse width 50nsec (Min.)
t
PWL : Low-level count input pulse width
50nsec (Min.)
t
PWH
CAUTION