8.8
Connecting the temperature sensors
Insert the temperature sensors through the openings from
outside into the immersion sleeves:
Push the sensor installation aid through the hole in the
insulation onto the immersion sleeve (as far as possible).
Insert the sensor
Hold the sensor in the immersion sleeve by the wire
while pulling out the sensor installation aid.
IMPORTANT
The sensors must be pushed in as far as possible
Seal the holes care-
fully with the
foam
plugs for sensors
∅
35
.
Screw the
sensor
cover
over the openings.
Connect the temperature sensors to the controller in ac-
cordance with the operating instructions of the corre-
sponding controller.
Route the sensor cables and 230 V cables in separate or
partitioned cable conduits.
Electrical installation work may only be performed by
professionals.
9
Operating instructions
9.1
Commissioning
Before commissioning the storage tank, the following pre-
conditions must be met:
Hydraulic installation of the storage tank has been com-
pleted.
The storage tank is completely filled and vented.
All controller inputs and outputs are connected.
All controller outputs have been checked for function.
All inputs of the sensors have been checked and display
plausible values.