UNIWORLD Series
M/UNIWORLD-M/E ed. 01 2020
3.5
– “BASIC VERSION” INTERNAL SWITCHES
The valves are supplied calibrated and tested, ready to work in the conditions requested by the client during the order phase. The
standard internal switches are used to block the motor in opening and closure by torque and stroke.
3.5.1
– BASIC VERSION” INTERNAL SWITCHES PSL201-214
3.5.1.1
– BASIC VERSION” INTERNAL SWITCHES FORCE / STROKE
To disconnect the limit switch depending on the force, the limit switches can be set using the spring joint compression “s”.
To carry out this operation, use the manual command handwheel:
Turn the handwheel until the
plug closes, then
Open the closure screw and
adjust the gear screw until it
clicks at end of stroke, then
tighten the closure screw
②
1 = opening position – stem withdrawn
2 = closure position – stem extended
Closure screw
Gear screw
①
Nut with milling
High limit position
Release position
Low limit position
Nut with milling