44
5.6.4 Inserting the EL2 Card
All important operating parameters such as the maximum steam capacity and the heating voltage
are permanently stored on the EL2 Card.
Before you start the electrical installation,
check whether the EL2 Card is installed
. If it is not,
check whether the type designation on the EL2 Card supplied corresponds with the type
designation on the data plate inside the unit
. If the designations match, place the EL2 Card in
the card holder on control print . Then cover the data plate above the type plate inside the unit with
the data plate supplied (self-adhesive).
If the type designation on the EL2 Card and the data plate do not match, the EL2 Card must not be
installed. If this is the case, contact your Condair supplier.
5.6.5 Inspecting the electrical installation
Check the following points:
Do the supply voltages for heating and control comply with the relevant voltages given in the
wiring diagram?
Is the correct EL2 Card inserted?
Are the voltage supplies (heating and control voltage) correctly fused?
Is the service switch “Q..” installed in the supply line for to the heating and control voltage?
Are all components correctly connected according to the wiring diagram?
Are all connecting cables fastened?
Are the connecting cables free of tension (passed through cable glands?)
Does the electric installation meet the applicable local regulations for electric installations?
Is the front panel mounted and correctly fixed with the two screws?