In positioning the steam distribution pipes, the following dimensions should be observed:
h
min
h
min
1/2
H
1/2
H
1/3
2/3
H
H
2/7
2/7
3/7
1/3
H
1/3
1/3
2/7
2/7
3/7
H
1/2
1/2
h
min
g
min
g min.= 100 mm
h min.= 85 mm
H min.= 250 mm
H ≥400 mm
H min.= 200 mm
H min.= 400 mm
H min.= 350 mm
H min.= 300 mm
5.4.3 Installing the steam distributors
Detailed information on the installation of steam distribution pipes 41-.., 61-.../81-... and OptiSorp
steam distribution system can be found in the separate mounting instructions for this products.
Note
: When locating the OptiSorp steam distribution system please note the instructions in the
separate documentation for this product.
Guidelines for dimensioning the ventilation ducts
– To facilitate the installation of the steam distribution pipes and for control purposes, a sufficiently
sized control opening should be planned.
– Within the range of the humidification distance, the ventilation duct should be waterproofed.
– Air ducts passing through cold rooms should be insulated to prevent the humidified air from con
-
densing along the duct wall.
– Poor airflow conditions within the air duct (e.g. caused by obstacles, tight bends, etc.) can lead
to condensation of the humidified air.
– Steam distribution pipes must not be mounted to round ducts.
If you have questions relating to the dimensioning of ventilation ducts in combination with steam