10
Turn off delay
In the activated state, if the output of the socket is switched on, in
order to keep the valve(s) open of the given heating circuit during the
pump circulation, the output of the socket switches off after a delay of
6 minutes from the switch-off signal of the last thermostat. The delay
is especially recommended if the zone valves are opened/closed by
quick-acting motorized actuators, as their opening/closing time is only
a few seconds. Activating the function in this case ensures that the
heating circuits are opened during the circulation of the pump and thus
protects the pump from overload. The function is only activated if the
last thermostat sends a switch-off signal to the socket.
The active status of the Turn off delay function is indicated by the red
LED flashing with 3-second intervals while the red LED is still lit.