After turning the main switch from position “1” to position “0”, the status indicator on the
control panel should go out.
5. Adjusting and maintenance
5.1 Hot gas bypass valve adjustment
At partial load, the valve directly returns a part of the hot gas to the suction line of the
refrigerating compressor.
The evaporation temperature and the evaporation pressure remain constant.
The hot gas by-pass valve is adjusted during the manufacturing testing phase.
As a rule no adjustment is required.
Anyway if it is necessary, the adjustment must be carried out by an experienced refrigerat-
ing engineer.
Without compressed air flow through the dryer, rotate the adjusting screw (position A on the
drawing) until the following value is reached:
Fig
. 5.1. Bypass valve. Regulating screw A.
Summary of Contents for 14310000
Page 52: ...52 2 2 1 1 1 1 2 1 2 3 Comprag 4 5...
Page 53: ...53 COMPRAG RDX 6 1 3 1 2 3 4 5 6 7 8 9...
Page 54: ...54 2 2 10 11 12 1 4 1 2 3...
Page 55: ...55 COMPRAG RDX 4 5 6 90 A 7 8 1 5...
Page 56: ...56 2 2 1 2 3 4 5 6 7 8 1 3 9 9 10 11 12 13 14 15 16...
Page 60: ...60 2 2 2 3 2 1 9 6 5 8 7 3 4 1 2 3 4 5 6 7 8 9 1 3 5 6 2 7 3 C...
Page 62: ...62 2 2 3 3 1 D H L 3 1 3 2...
Page 64: ...64 2 2 3 4...
Page 66: ...66 2 2 3 5 3 5 1 V 2 C RDX 04 77 5 M1 S1 M2 F1 A1 V1 S1 F...
Page 68: ...68 2 2 4 4 1 3 www comprag com RDX 3 2 1 4 1 1 V 2 RDX 04 18 1 2 3 3...
Page 71: ...71 COMPRAG RDX 1 2 4 1 4 V 2 1 2...
Page 72: ...72 2 2 4 2 8 1 2 4 1 1 4 1 2 4 1 3 4 3 4 3...
Page 73: ...73 COMPRAG RDX 1 2 3 4 3 1 2 3...
Page 74: ...74 2 2 5 5 1 R134a 2 2 0 1 0 R404a 5 4 0 1 0 5 1...
Page 75: ...75 COMPRAG RDX 5 2 1 2 3 5 2 1 2 3 2 3 1...
Page 76: ...76 2 2 6 6 1 30 4 1 5 3 1...
Page 77: ...77 COMPRAG RDX 5 3 5 3 4 3 5 3...
Page 78: ...78 2 2 7 7 1 10 25 85 7 2...
Page 79: ......
Page 80: ......