Specifications
Server Blade Enclosure
Table F-1: Enclosure Operating and Performance Specifications
Dimensions
Height
13.34 cm (5.25 in)
Depth
68.58 cm (27 in)
Width
48.26 cm (19 in)
Weight with patch panel
No server blades
26.76 kg (59 lb)
20 server blades
42.64 kg (94 lb)
Input requirements
Rated input voltage
100 to 127 VAC (200 to 240 VAC)
Rated input frequency
47 to 63 Hz
Rated input current
8.5A at 120 VAC (4.3A at 240 VAC)
Rated input power
1000 W
BTUs per hour
3416
Temperature range
1
Operating
10
°
to 35
°
C (50
°
to 95
°
F)
Shipping, 72 hours
-40
°
to 60
°
C (-40
°
to 140
°
F)
Relative humidity
(noncondensing)
2
Operating
10% to 90%
Non-operating
10% to 95%
1
Operating temperature has an altitude derating of 1°C per 304.8 m (1.8°F
per 1000 ft). No direct sunlight.
2
Storage maximum humidity of 95% is based on a maximum temperature of
45°C (113°F). Minimum pressure for storage is 70 KPa.
F-2