Fuel leaks from drain hoses. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the pressure in fuel tank too 

high? 

NO 

NO 

YES 

Is the carburetor  drain in bowl 

not closed? 

Contact  with  an  authorized 

dealer 

 

Turn  drain  screw  clockwise  to 

close 

Open fuel tank vent to balance 

pressure 

 

YES 

NO 

YES 

Is the fuel tap not closed while 

tilting the generator? 

Turn off the fuel tap 

Summary of Contents for COMP2100W

Page 1: ...User Manual 2100W INVERTER GENERATOR Model COMP2100W...

Page 2: ...FUEL 16 5 STARTING THE ENGINE 17 5 1 CHECK ENGINE OIL 18 5 2 CHECK FUEL 19 5 3 OPEN THE FUEL CAP VENT LEVER 20 5 4 OPEN THE FUEL TAP 21 5 5 THE ENGINE SWITCH ECO SWITCH 22 5 6 USE CHOKE 23 5 7 START...

Page 3: ...PARK ARRESTER MAINTENANCE 45 10 5 CLEANING FUEL TANK FILTER 47 11 TRANSPORTATION AND STORAGE 48 11 1 DRAIN THE FUEL FROM THE CARBURETOR 49 11 2 DRAIN THE FUEL FROM FUEL TANK 50 11 3 DRAIN THE FUEL FRO...

Page 4: ...ially closed area where people may be present The generator is a potential source of electrical shock if misused Do not expose the generator to moisture rain or snow Do not let the generator get wet a...

Page 5: ...This manual will provide you with a good basic understanding of the operation and maintenance of this machine We continually seek advancements in product design and quality Therefore while this manual...

Page 6: ...d it carefully These signal words mean This manual is filled with important safety information please read it carefully If you have any questions please consult an authorized dealer You WILL be KILLED...

Page 7: ...n and pets are not likely to touch Do not let children operate the generator Turn OFF the Fuel Tap before tilting the generator The generator is allowed to be tilted down but ONLY lay on the Drawbar S...

Page 8: ...UMES HAZARDS Exhaust fumes contains poisonous carbon monoxide CO a colorless and odorless gas Breathing CO can cause loss of consciousness and may lead to death Never run your generator inside a garag...

Page 9: ...E AND BURN HAZARDS Petrol is extremely flammable and explosive under certain conditions Do not smoke or allow flames or sparks where the generator is refueled or where petrol is stored Refuel in a wel...

Page 10: ...terials near the exhaust outlet during operation Keep the generator at least 1 m from buildings or other equipment or the generator may overheat Let the engine cool before storing the generator indoor...

Page 11: ...10...

Page 12: ...11 3 UNIT DESCRIPTION 3 1 COMPONENTS IDENTIFICATION 1 Control Panel Location of generator controls and output receptacles 1 2 3 4 8 5 6 7 12 10 11 13 9 18 18 16 15 14 17 7...

Page 13: ...nance Cover Allows access to air filter carburetor and engine oil cap etc 10 Spark Plug Maintenance Cover Allows access to engine spark plug 11 Oil Maintenance Cover Allows access to fill the engine o...

Page 14: ...C automotive style batteries while generator is in operation 4 12V DC Circuit Breaker Overload protection for the 12VDC charging system 5 USB Plug USB Output Sockets for connecting 5VDC devices 6 Para...

Page 15: ...r is producing electrical power at the receptacles 13 OVERLOAD LED red If the generator is overloaded or if there is a short circuit at AC Sockets the overload LED light red will go ON and current to...

Page 16: ...R LIMIT and UPPER LIMIT Too much or too little oil will shorten the service life of the engine The engine is equipped with a low oil sensor that will prevent the engine from running If the oil level f...

Page 17: ...and expands Immediately wipe off spilled fuel with a clean dry soft cloth since fuel may deteriorate painted surfaces or plastic parts Add Fuel 1 Remove the Fuel Cap 1 and fill the fuel into the tank...

Page 18: ...17 Make certain the generator is on a flat level surface Fuel tank capacity 4 2L 5 STARTING THE ENGINE...

Page 19: ...nnot reach L position the oil level is too low Fill to the upper limit of the oil filler neck with the recommended oil 5 Tighten the Oil Cap 2 and reinstall the Oil Maintenance Cover 1 6 Check generat...

Page 20: ...ank through the Fuel Gauge 1 If the red mark in the Fuel Gauge 1 is close to E position means the fuel level in the fuel tank is lower If the red mark in the Fuel Gauge 1 is close to F position means...

Page 21: ...20 5 3 OPEN THE FUEL CAP VENT LEVER Turn the Fuel Cap Vent Lever 1 to ON position 1 OFF position ON position ON OFF ON OFF...

Page 22: ...21 5 4 OPEN THE FUEL TAP Turn the Fuel Tap 1 to ON position 1 OFF position ON position...

Page 23: ...22 5 5 THE ENGINE SWITCH ECO SWITCH 1 Turn the Engine Switch Red 1 to ON position 2 Turn the ECO Switch Black 2 to OFF position 1 2 OFF position ON position...

Page 24: ...y 2 pulls of the recoil starter or 2 pushes of the electric start button After second pull or push push Choke Knob into the RUN position for up to the next 3 pulls or pushes Too much choke leads to sp...

Page 25: ...ted area Never run your generator inside a garage or house even if door or window is open NOTE Make certain the generator is on a flat level surface when start or operate the generator Turn off or unp...

Page 26: ...to prevent damage to the starter or housing Normally the engine can be started within three pulls Keep the Choke Knob in START position for only 2 pulls After second pull push the Choke Knob into the...

Page 27: ...After second push push the Choke Knob into the RUN position for up to the next 3 pushes The electric starter optional equipment is equipped with an over temperature sensor that will shut down the ele...

Page 28: ...fter starting the engine push the Choke Knob 1 fully into the RUN position NOTE Wait a few seconds until the engine speed is stable before closing the choke and wait longer if weather is cold 1 START...

Page 29: ...ADY LED green 4 comes on 2 Turn the ECO Switch 1 to ON position to use Economy Control System This system controls the engine speed according to the connected load The results are better fuel consumpt...

Page 30: ...ore connection to the generator Be sure the total load is within generator rated output Be sure the load current is within rated current If the generator is overloaded in excess of rated power or if t...

Page 31: ...t or turn off all electrical loads connected to the generator AC Sockets 1 2 Turn the Fuel Tap 2 to the OFF position 3 Turn the Engine Switch 3 to OFF position 4 Allow the engine to cool well then tur...

Page 32: ...ng the generator TURN OFF all electrical loads connected to the generator AC Sockets 1 before shutting down by Generator APP in smartphones Always allow the generator to cool off before moving or stor...

Page 33: ...ery while charging Sparks may ignite the battery gas Batteries give off explosive hydrogen gas while recharging Provide adequate ventilation when charging or using batteries Wear protective goggles an...

Page 34: ...ck 4 to positive battery terminal and the Black Charger Jack 5 to negative 4 Turn the ECO Switch 3 to the OFF position 5 Start the engine to charge the battery 6 Charging time will vary with battery s...

Page 35: ...tinue charging and contact your authorized generator dealer 7 2 DISCONNECTING THE BATTERY CHARGING CABLE 1 Turn the Engine Switch to OFF position to stop the engine 2 Disconnect the Black Charger Jack...

Page 36: ...ckets of the Parallel Kit 2 5 Turn on the appliance to use Parallel Terminal 1 output voltage is very high operators must be protected from electric shock at all times Do not operate with wet hands Do...

Page 37: ...power of two generators Most motorized appliances require more than their rated wattage for startup When an electric motor is started the OVERLOAD LED red 5 may come on This is normal if the OVERLOAD...

Page 38: ...t 2 before shutting down using Generator APP in smartphones 9 SPECIAL REQUIREMENTS NOTE DO NOT modify the generator in any way The generator is allowed to be tilted down but ONLY lay on the Drawbar Si...

Page 39: ...ling the engine Allow the engine to cool well if not the fuel tank can be crushed by cold contraction of the fuel gas in the fuel tank Keep all cooling holes open and clear of debris mud water etc Coo...

Page 40: ...Use only a nonflammable solvent not petrol to clean parts Keep cigarettes sparks and flames away from all fuel related NOTE If you are not familiar with maintenance work have an authorized dealer do i...

Page 41: ...n used in dusty areas 3 These items should be serviced by your servicing dealer unless you have the proper tools and are mechanically proficient 4 Replace fuel line if necessary every 2 years 5 For co...

Page 42: ...used oil into the container by tipping the engine toward the Oil Filler Neck 3 6 With the engine in a level position fill to the UPPER LIMIT of the Oil Filler Neck 3 with the recommended oil 7 Reinsta...

Page 43: ...ating the generator in extremely dusty areas Using petrol or flammable solvent to clean the air filter can cause a fire or explosion Use only soapy water or nonflammable solvent NOTE Operating the eng...

Page 44: ...or high flash point solvent Allow the air filters to dry thoroughly 4 Reinstall the Sponge 4 and Air Filter Cover 3 and tighten the Cover Screw 2 5 Reinstall the Maintenance Cover 1 10 3 SPARK PLUG SE...

Page 45: ...the Spark Plug 3 Replace it if the electrodes are worn or if the insulator is cracked chipped 5 Measure the spark plug electrode gap with a wire type feeler gauge Correct the gap if necessary by caref...

Page 46: ...rn after the spark plug seats to compress the washer 8 Reinstall the Spark Plug Cap 2 on the Spark Plug 3 securely 9 Reinstall the Spark Plug Maintenance Cover 1 NOTE A loose spark plug can overheat a...

Page 47: ...46 Five Screws 1 Screen B Screen A 1...

Page 48: ...park Arrester 1 3 Use a brush to remove carbon deposits from the Screen A and B 4 Inspect the Screen A for breaks or tears and replace it if necessary 5 Reinstall the Spark Arrester 1 and the Back Cov...

Page 49: ...ng or storing 3 Close the Fuel Cap tightly 4 Turn OFF the Fuel Cap Vent Lever DO NOT turn the Fuel Cap Vent Lever to OFF position before cooling the engine Allow the engine to cool well if not the fue...

Page 50: ...49 11 1 DRAIN THE FUEL FROM THE CARBURETOR 1 Turn the Fuel Tap 5 to the OFF position 1 2 3 4 1 OFF position ON position 5 5 Loosen Five screws...

Page 51: ...e petrol from the Carburetor 2 into the container through the Drain Hose 1 6 Tighten the Drain Screw 3 clockwise securely 11 2 DRAIN THE FUEL FROM FUEL TANK 1 Unscrew the Fuel Cap remove the Fuel Tank...

Page 52: ...l from the Carburetor 2 into the container through the Drain Hose 1 6 Tighten the Drain Screw 3 clockwise securely 7 Reinstall the Drain Hose 1 into the hole at the bottom casing 8 Reinstall the Maint...

Page 53: ...ion then stop pulling This prevents the cylinder and valves from rusting 5 Clean the generator outer surfaces Check that cooling air slots and openings on generator are open and unobstructed 6 Store t...

Page 54: ...ot start contact with an authorized dealer Add the recommended oil Clean readjust gap and dry the spark plug Replace it if necessary YES YES YES NO NO YES NO Is the fuel in the carburetor good Turn an...

Page 55: ...cap vent lever closed Open fuel cap vent lever Is engine oil level incorrect Check engine oil level add or drain as needed Is the fuel in the fuel tank contaminated Replace fuel in the fuel tank clea...

Page 56: ...oke stuck or left on Is the air cleaner dirty or clogged Is the spark plug defective or dirty Contact with an authorized dealer Turn choke to run position Clean or replace the air filter element Repla...

Page 57: ...t with an authorized dealer Reduce loads and push reset button to reset module Verify the choke is on run position and check fuel in the fuel tank and carburetor and check air filter Verify condition...

Page 58: ...appliance for any faults Is the DC circuit protector OFF Push the DC circuit protector ON Change or replace the appliance Contact with an authorized dealer NO YES YES Is the DC voltage low Verify ECO...

Page 59: ...too high NO NO YES Is the carburetor drain in bowl not closed Contact with an authorized dealer Turn drain screw clockwise to close Open fuel tank vent to balance pressure YES NO YES Is the fuel tap...

Page 60: ...OHV Cooling System Forced air Cylinder Arrangement Inclined single cylinder Displacement 79cm3 Bore Stroke 48 6mm 43 0mm 1 91 in 1 69 in Operation Hours 3 5Hr rated load 8Hr 1 4 rated load Fuel Unlead...

Page 61: ...um Output 2 1kVA Safety Device Type Electronic DC Output Rated Voltage 12V Rated Current 8A USB 5V 2A 1A Safety Device Type DC Protector NOTE 1 COMP2100W is equipped with recoil starter electric start...

Page 62: ...61 14 WIRING DIAGRAM COMP2100W...

Page 63: ...62 COMP2100W...

Page 64: ...0 89 0 87 0 84 1000 0 87 0 85 0 82 0 80 0 78 2000 0 75 0 73 0 71 0 69 0 66 3000 0 64 0 62 0 60 0 58 0 56 4000 0 52 0 52 0 50 0 48 0 46 NOTE Relative humidity 60 correction factor C 0 01 Relative humi...

Reviews: