www.commscope.com
860452168
Instruction Sheet
Page 9 of 21
Step 4 – Install Termination Devices
Note:
Modular cassettes, bezels, and adapter panels are normally ordered separately from the shelf. Some
customer specific versions of this shelf come pre-terminated and will not require these steps.
Step 4A – G2 Modular Cassette Application
1. Starting at location A (the left-most position), plug a cassette into the bulkhead cutout until it snaps into
place, as shown in figure above.
2. Remove cassette cover and spool out enough length from the pigtails that they may be routed into the slack
fiber management rings and have sufficient length for subsequent splicing operations. Spool fiber into slack
management rings as shown. Replace cover.
3. Repeat items 1 and 2 for the next five consecutive cassette locations (locations B through F).
4. Starting at location G (seventh location from the left side), repeat items 1 and 2 for all remaining locations
(locations G through M).
5. Pigtails from locations A through F are to be spooled into the first set of slack fiber management rings (four
rings on the left-hand side of the shelf). Fibers from locations G through M are to be spooled into the second
set of slack fiber management rings (four rings on the right-hand side of the shelf).