Step 2 – Configure Mounting Brackets and Mount Shelf to Equipment Rack
1. Configure mounting brackets to match type of equipment rack to be used as shown above.
2. Align tabs on mounting brackets (two per bracket) with the holes on the front of equipment rails.
Note
: If tabs do not insert into holes in equipment rails without interference, DO NOT FORCE as damage to
shelf will result. In this case, tabs must be bent back or trimmed off to eliminate interference. This situation
is usually caused by equipment racks/cabinets being improperly assembled. Great care should be taken
when assembling racks/cabinets to assure that the rails are properly aligned. Use of an alignment tool is
recommended.
3. Install shelf to front of equipment rails using four 12-24 x 1/2-inch screws (provided) for 19-inch (483mm)
rack and 23-inch (584mm) racks and four M6 x 12 screws for ETSI racks. See figure below.
Configuration for 19” Rack
Configuration for 23” Rack
Configuration for ETSI Rack
For ETSI configuration only,
use these holes to secure
mounting bracket on right side
Front
Side View