ADCP-92-098 • Rev C • May 2018
Page 11
© 2018
CommScope
. All Rights Reserved.
2.5
Panel Grounding
Each panel has a grounding location marked with the standard grounding symbol. This location
is on the right side of the panel (see
Figure 10
). Use the two 10-32 screws and star washers
provided to attach a 2-hole lug terminal at the grounding location, as shown in
Figure 11
.
Follow local practice.
Figure 10. Grounding Location
(Rear View of Panel)
Figure 11. Ground Stud
Note:
Ground the unit to the local facility CBN (Common Bonding Network) or IBN
(Isolated Bonding Network) per local practice.
GROUNDING
LOCATION
23947-B
24016-A
2-HOLE LUG
TERMINAL
COPPER WIRE
STRIP BACK INSULATION
PER LUG MANUFACTURER'S
RECOMMENDATION
HOLE CENTER
SPACING:
0.625 INCHES