Installation
To install the Matrix panel, follow these steps:
1.
Select the equipment rack location for installation of the panel.
Orient the rack mount ears appropriately for a 19”
or 23” rack. For flush mounting, install the rack mount ears using the included Phillips head screws through the two
holes near the front of the panel. To offset-mount the panel such that the front protrudes beyond the front plane of the
rack, use the two holes further back on the sides of the panel.
2.
Install the chassis ground cable.
A chassis
ground cable should be landed on the two
studs marked Chassis Ground on the left
side of the panel.
3.
Install the incoming DC feeder cables for
the A and B power inputs and A and B
power returns.
Consider installing a piece of clear
heatshrink tubing (3” diameter x 6” long)
over each of the power cables prior to
bolting the cable lugs to the bus bars.
Secure the cable lugs to the bus bars with
the included ¼”-20 x 1” bolts, flat washers,
lock washers, and nuts. The bus bars have
a hole and a slot to allow for ¾” or 1” bolt
hole spacing.