S E T U P   A N D   O P E R A T I O N   M A N U A L  

Page 8 

With the magnet in place, the breaker extraction tool is designed to attach directly 
to the metal chassis of the panel. When not in use the breaker extraction tool 
should be attached to the front of the panel for direct and consistent access. 

 

 

Extracting Slimline Breakers 

Each slimline breaker has two threaded brass screw hole features designed for 
extraction. 

 

 

The breaker extraction tool is fitted with screw features designed to attach to the 
breaker. Attach the breaker extraction tool to the front of the breaker with these 
screws. 

 

 

Attach the breaker extraction tool to the front of the slimline breaker. 

 

 

With your finger on the breaker extraction tool, slowly pull the breaker extraction 
tool directly away from the breaker panel to release the breaker from the panel. 

 

 

 

Summary of Contents for Matrix 016-131-10

Page 1: ...Matrix 1RU High Power Density DC Distribution Center SETUP AND OPERATION MANUAL S E T U P A N D O P E R A T I O N M A N U A L...

Page 2: ...ed at the factory to withstand the normal rigors of shipping However you should carefully inspect the box and contents to confirm that no damage occurred in transit Most shipping carriers require noti...

Page 3: ...rack use the two holes further back on the sides of the panel 2 Install the chassis ground cable A chassis ground cable should be landed on the two studs marked Chassis Ground on the left side of the...

Page 4: ...on corresponding to the output channel to be fed viewing the front of the panel from left to right the positions are A1 A2 A3 A4 A5 A6 A7 A8 then B1 B2 B3 B4 B5 B6 B7 B8 Push until the circuit breaker...

Page 5: ...ory Button The Breaker Inventory Button when held for more than five seconds is used to store the breaker inventory in nonvolatile memory The button may also be used to temporarily silence indefinitel...

Page 6: ...is turned off the red Breaker Trip LED will turn on and the alarm beeper will sound When the breaker is turned back on the LED will turn off and the alarm beeper will silence 4 The breaker inventory...

Page 7: ...successful Panel and Breaker Rating Limitations The panel is rated for a maximum current of 300A per bus The sum of the eight distribution breakers on either side of the panel may not exceed 300A The...