ComfortStar CPP012CD(O) Installation Manual Download Page 14

CAUTION 

CAUTION 

-76 c mHg 

Lo-lev er 

Hi-leve r 

Charg e hos e 

Charg e hos e 

Vac uum p ump 

Lo-lev er 

Manifo ld valv e 

Multi-m eter  Pressu re  meter 

Fig.8-7

Refrigerant cannot be charged until field wiring has been 
completed.

Refrigerant may only be charged after performing the leak 
test  and the vacuum pumping.

When charging a system, care shall be taken that its 
maximum permissible charge is never exceeded, in view of 
the danger of liquid hammer.

Charging with an unsuitable substance may cause 
explosions and accidents, so always ensure that the 
appropriate refrigerant is charged.

Refrigerant containers shall be opened slowly.

Always use protective gloves and protect your eyes when 
charging refrigerant.

Ventilate the air if there was any refrigerant leakage 
during the installation.
Leaked refrigerant will generate poisonous gas if 
meeting fire.

Make sure there is no refrigerant leakage after the 
installation.
Leaked refrigerant will generate poisonous gas if 
meeting fire.

Allowed Lenght and Drop of Pipes

Requirements are different when installing the outdoor unit, 
please refer to outdoor unit installation manual for detailed 
information.

Material and Size of the Pipes

8.2.   Refrigerant pipe installation

NOTE 

Drainage test 

Drainage test 

Check whether the drainpipe is unhindered. 

New built house should have this test done before paving 
the ceiling. 

Remove the test cover, and stow water of about 2000ml to the 
water receiver through the stow tube.  

Turn on the power, and operate the air conditioner under the 
"COOLING" mode. Listen to the sound of the drain pump. 
Check whether the water is discharger well (a lag of 1min is 
allowed before discharging, according to the length of the drain 
pipe), and check whether water leaks from the joints. 

Stop the air conditioner, turn off the power, and reset the test 
cover to its original position. 

The drain plug is used to empty the water-receiver for 
maintenance of the air conditioner. Please stuff it imposition at 
all times during operation to avoid leakage. 

The body's pump pipe and the drainpipe (especially the 
indoor part) should be covered evenly with the out-let pipe 
sheath (fittings) and be bound tightly with the constrictor to 
prevent condensation caused by entered air. 

To prevent water from flowing backwards into the air 
conditioner while the air conditioner stops, please lean the 
drainpipe down toward outdoor (outlet-side) at a degree of 
over 1/ 50. And please avoid any bulge or water deposit.        

 

Do not drag the drainpipe violently when connecting to 
prevent the body from being pulled. Meanwhile, one 

drainpipe from yielding.Or you can tie the drainpipe with the 
connecting pipe to fix it.

 

In the case of prolonged drainpipe, you had better tighten its 
indoor part with a protection tube to prevent it from loosing. 

If the outlet of the drainpipe is higher than the body's pump 
joint, the pipe should be arranged as vertically as possible. 

water will overflow when the air conditioner stops.

 

The end of the drainpipe should be over 2.0inch higher than 
the ground or the bottom of the drainage chute, and do not 
immerse it in water. If you discharge the water directly into 
sewage, be sure to make a U-form aquaseal by bending the 
pipe up to prevent the smelly gas entering the house through 
the drain pipe. 

9.    CONNECT THE DRAIN PIPE

Install the drainpipe of the indoor unit 

You can use a polyethylene tube as the drainpipe 

market or from your dealer. 
  
Set the mouth of the drainpipe onto the root of the body's 
pump-pipe, and clip the drainpipe and the out-let pipe sheath 
(fittings) together firmly with the out-let pipe clasp (fitting). 

13

installation manual 

Three length(9.8ft,16.4ft,32.8ft)of pipes are available to purchase. 

And the lift distance must be less than 7.8inch, otherwise the 

supportpoint should be set every 3.3~4.9ft to prevent the 

(out-dia.1.46-1.54in, in-dia.1.26in). It could be bought at local 

Summary of Contents for CPP012CD(O)

Page 1: ...PA 12 TPA 18 TPA 24 TPA 36DU TPA 48DU Outdoor Unit CPP009CD O CPP012CD O CPP018CD O CPP024CD O CPP036CD O DU CPP048CD O DU If used as MULTI unit please refer to the Installation operation manuals pack...

Page 2: ...strong and firm location which is able to withstand the set s weight If the strength is not enough or installation is not properly done the set will drop to cause injury The appliance must be installe...

Page 3: ...not be sufficient enough to eliminate the noise The appliance is not intended for use by young children or infirm persons without supervision Don t install the air conditioner in the following locatio...

Page 4: ...vement without further notices Cautions on remote controller installation Remote controller Remote controller holder Mounting screw B ST2 9x10 C H CANCEL LOCK SET TEMPERATURE C AUTO COOL DRY HEAT FAN...

Page 5: ...INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the service agent When handling the unit take into account the following 5...

Page 6: ...y by wrenching the nuts after having adjusted the body s position well Refer to Fig 5 5 Select the position of installation hooks according to the hook holes on the installation board positions on the...

Page 7: ...our corners if the lift of the indoor unit and the drainpipe is not influenced Refer to Fig 5 13 right Hang the air in grill to the panel then connect the lead terminator of the swing motor and that o...

Page 8: ...ge test Check whether the drainpipe is unhindered New built house should have this test done before paving the ceiling The unit with pump Remove the test cover and stow about 2000ml water to the water...

Page 9: ...g 5 19 Fig 5 18 One way Two way In case of one duct connection In case of two duct connection NOTE Fig 5 17 5 4 Install the distribution duct Conditioned air can be distributes by means of a distribut...

Page 10: ...direct sunlight If necessary install a blind that does not interfere with the air flow During the heating mode the water drained off the outdoor unit The condensate should be well drained away by the...

Page 11: ...lve of vacuum meter 2 Cut off the connection between pressure meter and vacuum pump 3 Close the vacuum pump Fig 6 7 NOTE All the pictures in this manual are for explanation purpose only They may be sl...

Page 12: ...ell with the tapes to prevent leakage Execute heat insulation work completely on both sides of the gas piping and the liquid piping Otherwise this can sometimes result in water leakage 1 2 3 5 6 7 4 B...

Page 13: ...orque N M Turn clockwise to close Stop Valve size Shaft valve body Cap Valve lid 6 4 5 4 6 6 Hexagonal 13 5 16 5 11 5 13 9 9 5 12 7 8 1 9 9 18 22 15 9 13 5 16 5 Hexagonal 23 27 22 2 27 33 Hexagonal wr...

Page 14: ...ion 3 The drain plug is used to empty the water receiver for maintenance of the air conditioner Please stuff it imposition at all times during operation to avoid leakage The body s pump pipe and the d...

Page 15: ...ment has to be connected with this power line For detailed installation acceptance please refer to your power supplier if restrictions do apply for products like washing machines air conditioners or e...

Page 16: ...impeded The heating insulation works well The ground wiring is connected correctly The length of the tubing and the added stow capacity of the refrigerant have been recorded The power voltage fits the...

Page 17: ...ding to the wiring scheme or it damages the unit Before obtaining access to terminals all supply circuits must be disconnected CAUTION Indoor Outdoor connection The power supply must comply with the r...

Page 18: ...ls TECHNICAL BULLETIN Heat Sink Compound Thermal Paste Make sure to use Heat Sink Compound not provided when replacing Mini Split electronic boards Clean up thoroughly old paste on chips located under...

Reviews: