ComfortStar CPP012CD(O) Installation Manual Download Page 11

10

installation manual 

Fig.7-1 

Use the vacuum pump which vacuum level lower than  
-0.1MPa and the air discharge capacity above 40L/min. 
 
The outdoor unit is not necessary to vacuum, don’t open the 
outdoor unit gas and liquid pipe shut-off valves. 
 
Make sure the vacuum pump could result as -0.1MPa or 
below after 2 hrs or above operation. If the pump operated 3 
hrs or above could not achieve to -0.1MPa or below, please 
check whether water mix or gas leak inside of the pipe. 

7.1   Vacuum with vacuum pump 

1) 
 
 
2) 
 
 
3) 

CAUTION 

Don’t mix up the different refrigerants or abuse the tools and 
measurements which directly contact with refrigerants. 
 
Don’t adopt refrigerant gas for air vacuuming. 
 
If vacuum level could not get to -0.1MPa, please check whether 
resulted by leakage and confirm the leakage site.If no leakage, 
please operate the vacuum pump again 1 or 2 hrs.  

 

Connect with vacuum pump 

Perform the pump (last for 2 hrs or above) 

When get the vacuum level 
-0.1MPa, the pump should 
keep running for 20-60 mins 

Shut down the  
vaccun pump 

Place the vaccum state unused (1 hrs or above) 

1. Close-off the valve of 
vacuum meter. 
2. Cut off the connection 
between pressure meter 
and vacuum pump. 
3. Close the vacuum 
pump. 

Fig.6-7 

NOTE 

All the pictures in this manual are for explanation 
purpose only. They may be slightly different from the 
air conditioner you purchased(depend on model).The 
actual shape shall prevail. 

2.0ft

Fix with  bolt 

Never hold the inlet of the outdoor unit to prevent it from 
deforming. 
 
Do not touch the fan with hands or other objects. 
 
Do not lean it more than 45, and do not lay it sidelong. 
 
Make concrete foundation accoding to the sepecif-ications of 
the outdoor units.

(Refer to Fig.6-7) 

 
Fasten the feet of this unit with bolts firmly to prevent it from 
collapsing in case of earthquake or strong wind.

(Refer to 

Fig.6-15)

  

6.3   Moving and installation 

Since the gravity center of the unit is not at its physical 
center, so please be careful when lifting it with a sling. 

Model 

 

W1 

CPP009CD(O) 

mm 

770 

300 

555 

840 

487 

298 

inch 

30.3 

11.8 

21.9 

33.1 

19.2 

11.7 

CPP012CD(O) 

mm 

800 

333 

554 

870 

514 

340 

inch 

31.5 

13.1 

21.8 

34.3 

20.2 

13.4 

CPP018CD(O) 

mm 

845 

363 

702 

914 

540 

350 

inch 

33.3 

14.3 

27.6 

36.0 

21.3 

13.8 

CPP024CD(O) 

CPP036CD(O)-DU 

mm 

946 

410 

810 

1030 

673 

403 

inch 

37.2 

16.1 

31.9 

40.6 

26.5 

15.9 

CPP048CD(O)-DU 

mm 

952 

415 

1333 

1045 

634 

404 

inch 

37.5 

16.3 

52.5 

41.1 

25.0 

15.9 

Summary of Contents for CPP012CD(O)

Page 1: ...PA 12 TPA 18 TPA 24 TPA 36DU TPA 48DU Outdoor Unit CPP009CD O CPP012CD O CPP018CD O CPP024CD O CPP036CD O DU CPP048CD O DU If used as MULTI unit please refer to the Installation operation manuals pack...

Page 2: ...strong and firm location which is able to withstand the set s weight If the strength is not enough or installation is not properly done the set will drop to cause injury The appliance must be installe...

Page 3: ...not be sufficient enough to eliminate the noise The appliance is not intended for use by young children or infirm persons without supervision Don t install the air conditioner in the following locatio...

Page 4: ...vement without further notices Cautions on remote controller installation Remote controller Remote controller holder Mounting screw B ST2 9x10 C H CANCEL LOCK SET TEMPERATURE C AUTO COOL DRY HEAT FAN...

Page 5: ...INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the service agent When handling the unit take into account the following 5...

Page 6: ...y by wrenching the nuts after having adjusted the body s position well Refer to Fig 5 5 Select the position of installation hooks according to the hook holes on the installation board positions on the...

Page 7: ...our corners if the lift of the indoor unit and the drainpipe is not influenced Refer to Fig 5 13 right Hang the air in grill to the panel then connect the lead terminator of the swing motor and that o...

Page 8: ...ge test Check whether the drainpipe is unhindered New built house should have this test done before paving the ceiling The unit with pump Remove the test cover and stow about 2000ml water to the water...

Page 9: ...g 5 19 Fig 5 18 One way Two way In case of one duct connection In case of two duct connection NOTE Fig 5 17 5 4 Install the distribution duct Conditioned air can be distributes by means of a distribut...

Page 10: ...direct sunlight If necessary install a blind that does not interfere with the air flow During the heating mode the water drained off the outdoor unit The condensate should be well drained away by the...

Page 11: ...lve of vacuum meter 2 Cut off the connection between pressure meter and vacuum pump 3 Close the vacuum pump Fig 6 7 NOTE All the pictures in this manual are for explanation purpose only They may be sl...

Page 12: ...ell with the tapes to prevent leakage Execute heat insulation work completely on both sides of the gas piping and the liquid piping Otherwise this can sometimes result in water leakage 1 2 3 5 6 7 4 B...

Page 13: ...orque N M Turn clockwise to close Stop Valve size Shaft valve body Cap Valve lid 6 4 5 4 6 6 Hexagonal 13 5 16 5 11 5 13 9 9 5 12 7 8 1 9 9 18 22 15 9 13 5 16 5 Hexagonal 23 27 22 2 27 33 Hexagonal wr...

Page 14: ...ion 3 The drain plug is used to empty the water receiver for maintenance of the air conditioner Please stuff it imposition at all times during operation to avoid leakage The body s pump pipe and the d...

Page 15: ...ment has to be connected with this power line For detailed installation acceptance please refer to your power supplier if restrictions do apply for products like washing machines air conditioners or e...

Page 16: ...impeded The heating insulation works well The ground wiring is connected correctly The length of the tubing and the added stow capacity of the refrigerant have been recorded The power voltage fits the...

Page 17: ...ding to the wiring scheme or it damages the unit Before obtaining access to terminals all supply circuits must be disconnected CAUTION Indoor Outdoor connection The power supply must comply with the r...

Page 18: ...ls TECHNICAL BULLETIN Heat Sink Compound Thermal Paste Make sure to use Heat Sink Compound not provided when replacing Mini Split electronic boards Clean up thoroughly old paste on chips located under...

Reviews: