R
C
W/B
O
Y
G
W2/E
Y2
SLP
SLP
SENSORS
TSTAT
HVAC
ODT
ODT
GND
+5V
SA
SB
LIVING SLEEP
SPACE SPACE
DMPR
DMPR
Description
Compatible Equipment, WH11
Power
Power Indicator
Damper Actuators
Wired Temperature Sensor
Wireless Temperature Sensor
The Wiring Hub is installed at the equipment. It is connected to
the C365C42 or C365C42WF thermostat using the existing or
new 4-wire thermostat cable that normally connects the
thermostat to the equipment. The equipment is wired directly to
the Wiring Hub. The upstairs sensor can be either a wired or
wireless sensor. Wireless sensors use the ELR1 Radio Module
that plugs into the Wiring Hub. An outdoor temperature sensor
can also be used to control fossil fuel heating in a dual fuel heat
pump (WH32 only).
Gas/Electric equipment with 1 heat/ 1 Cool.
Powered by 24VAC from the equipment R and C terminals
LED indicator.
Uses A80MJ Plug&Play damper Actuators. Up to 6 dampers
can be daisy chained to define the Upstairs Sleeping or
Downstairs Living area.
One or two wired sensors can be used in the upstairs sleeping
space. For single sensor installations use TS510W sensor. For
two-sensor installations, use two TS520W sensors.
One or two battery powered, wireless sensors can be used. The
ELR1 Radio Module must be installed in the Wiring Hub when
wireless sensors are used. Use the TS5WL sensor for 1 or 2-
sensor installations.
Installer Manual
Wiring Hub, Model WH11 and WH32
365
Comfort
Ver 2.40 Sep 2018
Screw attaches cover to base.
Cover.
Optional eLink Radio Module plugs into connectors.
24VAC Power Indicator.
Terminals for wiring
to HVAC equipment.
Terminals for Upstairs Remote
wired temperature sensor.
Terminals for optional outdoor
temperature sensor.
Terminals for wiring to
Comfort365 Thermostat.
Connector for Downstairs Living Space
Plug&Play Modulating Damper.
Connector for Upstairs Sleeping Space
Plug&Play Modulating Damper.
Compatible Equipment, WH32
Gas/Electric equipment, conventional and dual fuel heat pump
equipment with 3 heat/ 2 Cool.