background image

www.desatech.com

120163-01A

7

  * Do not include direct-vent gas appliances. 

Direct-vent draws combustion air from the 

outdoors and vents to the outdoors.

 

Example:

  Gas water appliance 

_________Btu/Hr

  Vent-free appliance 

+_________Btu/Hr

  Total 

=_________Btu/Hr

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

   ___________ Btu/Hr (maximum the space 

   

can support)

   ____________Btu/Hr (actual amount of

   

Btu/Hr used)

 

Example: 

51,200  Btu/Hr  (maximum  the  

 

space can support) 

   

73,000 Btu/Hr (actual amount of  

   

Btu/Hr used)

The space in the previous example is a confined 

space because the actual Btu/Hr used is more than 

the maximum Btu/Hr the space can support. You 

must provide additional fresh air. Your options 

are as follows:

A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides an 

unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. 

See 

Ventilation Air From Inside Building

.

B.  Vent room directly to the outdoors. See 

Ven-

tilation Air From Outdoors

.

C.  Install a lower Btu/Hr appliance, if lower 

Btu/Hr size makes room unconfined.

  If  the  actual  Btu/Hr  used  is  less  than  the 

maximum Btu/Hr the space can support, the 

space is an unconfined space. You will need 

no additional fresh air ventilation.

 WARNING: If the area in which 

the appliance may be operated 

is smaller than that defined as 

an  unconfined  space  or  if  the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 Section 5.3

 

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining 

unconfined space, you must provide two perma-

nent openings: one within 12" of the ceiling and 

one within 12" of the floor on the wall connecting 

the two spaces (see options 1 and 2, Figure 2). You 

can also remove door into adjoining room (see 

option 3, Figure 2). Follow the 

National Fuel Gas 

Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for 

Combustion and Ventilation

 for required size of 

ventilation grills or ducts.

40,000

33,000

73,000

AIR FOR COMbUSTION 

AND VENTILATION

Continued

Figure 2 - Ventilation Air from Inside 

Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12"

12"

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or 

ducts. You must provide two permanent openings: 

one within 12" of the ceiling and one within 12" 

of the floor. Connect these items directly to the 

outdoors or spaces open to the outdoors. These 

spaces include attics and crawl spaces. Follow the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, 

Section 5.3, Air for Combustion and Ventilation

 for 

required size of ventilation grills or ducts.

IMPORTANT:

 Do not provide openings for inlet 

or outlet air into attic if attic has a thermostat-

controlled power vent. Heated air entering the attic 

will activate the power vent.

Figure 3 - Ventilation Air from Outdoors

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Summary of Contents for CSM2618NR

Page 1: ...al switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire departmen...

Page 2: ...ce with ANSIZ21 11 2 Exception Donot install this appliance in a fac tory builtfireplacethatincludes instructions stating it has not been tested or should not be used with unvented gas logs WARNING Th...

Page 3: ...ns toblowdirectlyintothefireplace Avoidanydraftsthatalterburner flame patterns Ceiling fans can create drafts that alter burner flame patterns Altered burner patterns can cause sooting WARNING Do not...

Page 4: ...these products may create a white powder residue within the burner box or on adjacent walls and furniture 9 This heater needs fresh outside air ventilation to run properly this heater has an Oxygen De...

Page 5: ...in the Commonwealth of Massachusetts Product Features OPERATION This heater is clean burning It requires no outside venting There is no heat loss out a vent or up a chimney Heat is generated by both r...

Page 6: ...l Gas Code ANSI Z223 1 NFPA 54 defines a confined space as a space whose vol ume is less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kw of the aggregate input rating of all appliances install...

Page 7: ...hodsdescribed in the National Fuel Gas Code ANSIZ223 1 NFPA54Section5 3 or applicable local codes VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining un co...

Page 8: ...NING Seal any fresh air vents or ash clean out doors located on floor or wall of fire place If not drafting may cause pilot outage or sooting Use a heat resistant sealant Do not seal chimney flue damp...

Page 9: ...IREPLACE CLEARANCE TO COMBUSTIBLE MATERIALS SIDE WALL 16 CEILING 42 FLOOR 5 LOG SIZING REQUIREMENTS MINIMUM FIREBOX SIZE LOG SIZE HEIGHT DEPTH FRONT WIDTH REAR WIDTH 18 18 14 30 20 5 24 18 14 35 24 5...

Page 10: ...Figure 6 are not met you must have a hood When using a hood there are still certain minimum mantel clearances required Follow minimum clearances shown in Figure 7 when using hood Figure 6 Minimum Mant...

Page 11: ...ON Note When used as a vented decorative appliance must be installed only in a solid fuel burning fireplace with a working flue and constructed of noncombustible material For Massachusetts Residents O...

Page 12: ...s needed You must raise the fireplace floor to allow access to heater control panel This will insure adequate air flow and guard against sooting Raise fireplacefloorwithnoncombus tiblematerial Makesur...

Page 13: ...Tank External Regulator Figure 13 External Regulator With Vent Pointing Down Vent Pointing Down For propane LP units the installer must supply an external regulator The external regulator will reduce...

Page 14: ...pply piping system Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak 5 Correct all leaks at once 6 Reconnect heater and equipment shutoff valve to gas supply Check reco...

Page 15: ...ints Bubbles forming show a leak 5 Correct all leaks at once 6 Light heater see Operating Heater page 16 Check all other internal joints for leaks 7 Turn off heater Equipment Shutoff Valve Open Closed...

Page 16: ...lly within one minute when the switch is in the ON position after the pilot is lit 5 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B...

Page 17: ...Figure 15 page 15 MANUAL LIGHTING PROCEDURE 1 Follow steps 1 through 6 under Lighting Instructions page 16 2 Depress control knob and light pilot with match 3 Keep control knob pressed in for30 second...

Page 18: ...ime or as a child safety feature to prevent accidental ignition of the fireplace the receiver ON OFF REMOTE switch should be in the OFF position Auto Shutoff Feature 1 If the average room temperature...

Page 19: ...yellow color yellow decorative flames are visible as the flames exit the log set The base of the log set and the underside of the top logs glow red Natural gas models will burn with more blue flame wh...

Page 20: ...can please follow the directions on the can If you don t follow directions on the can you could damage the pilot assembly 1 Shut off the unit including the pilot Allow the unit to cool for at least t...

Page 21: ...pe Propane LP Only Ignition Piezo Manifold Pressure 10 6 3 W C Inlet Gas Pressure in of water Maximum 14 W C Minimum 11 W C For purpose of input adjustment Manufactured by DESA 1769 E Lawrence St Russ...

Page 22: ...ne LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tightennuthold...

Page 23: ...rol knob pressed in 30 seconds 3 Wait one minute for safety in terlock system to reset Repeat ignition operation 4 Fully open equipment shutoff valve 5 A Contact local natural or propane LP gas compan...

Page 24: ...2 Operate burners until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum instal lation clearances see pages 9 through 12 4 Clean burners see...

Page 25: ...logged 1 Gas leak See warning statement at top of page 2 Control valve or gas control defective 1 Foreign matter between con trol valve and burner 2 Gas leak See warning statement at top of page 1 Han...

Page 26: ...eater the replacement part number EQUIPMENT SHUTOFF VALVE GA5010 For all models Equipment shutoff valve with 1 8 NPT tap Fits 1 2 NPT pipe FIREPLACE HOOD Black GA6050 Brass GA6052 Antique Brass GA6053...

Page 27: ...r log pieces Control Cover Media Kit cc100 For all models This kit is used as an addition to or instead of the Floor Media Kit FM100 It includes 6 fiber log chunks to be placed on the fireplace floor...

Page 28: ...www desatech com 120163 01A 28 Illustrated Parts Breakdown Models CSM2618NR CSM2618PR CSM3624NR and CSM3624PR 1 4 5 3a 3b 6 9 11 2 12 13 16 18 8 19 22 7 10 20 17 14 15...

Page 29: ...pter 1 9 111804 01 Burner 1 111804 03 Burner 1 10 111819 04 Orifice 1 111819 05 Orifice 1 111819 14 Orifice 1 111819 15 Orifice 1 11 111807 01 Valve 1 111807 02 Valve 1 12 111796 01 Valve Bracket 1 13...

Page 30: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 31: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 32: ...odes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result...

Reviews: