INSTALLATION

Continued

Heat Resistant
Material 

(A)

Figure 5 - Heat Resistant Material (Slate, 

Marble, Tile, etc.) Above Fireplace

If Using Mantel

You must have noncombustible material(s) above 

the fireplace opening. Noncombustible materials 

(such as slate, marble, tile, etc.) must be at least 

1/2" thick. With sheet metal, you must have non-

combustible material behind it. Noncombustible 

material must extend at least 8" up (for all models). 

If noncombustible material is less than 12", you 

must install the fireplace hood accessory (24" 

Models Only). Even if noncombustible material is 

more than 12", you may need the hood accessory 

to deflect heat away from your mantel shelf. See 

Figures 5, 6 and 7 for minimum clearances.

MANTEL CLEARANCES

In addition to meeting noncombustible material 

clearances, you must also meet required clearances 

between fireplace opening and mantel shelf. If 

you do not meet the clearances listed below, you 

will need a hood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel 

shelf and top of fireplace opening, a hood is not 

required (see Figure 6).

Determining Minimum Mantel Clearance 
When Using a Hood

If minimum clearances in Figure 6 are not met, you 

must have a hood. When using a hood there are 

still certain minimum mantel clearances required. 

Follow minimum clearances shown in Figure 7 

when using hood.

Figure 6 - Minimum Mantel Clearances 

Without Using Hood

Figure 7 - Minimum Mantel Clearances 

When Using Hood

Noncombustible 

Requirements  for 

 

Material Distance (A)  Safe Installation

12" or more 

Noncombustible 
material OK.

Between 8" and 12" 

24" Models:

 

Install fireplace hood 

accessory (GA6050, 
GA6052, GA6053, see 

Accessories

, page 26).

 

18" Model: Noncom-
bustible material OK.

Less than 8" 

Noncombustible 
material must be 
extended to at least 
8". See 

Between 8" 

and 12"

, above. If you 

cannot extend material, 
you must operate 

heater with flue damper 

open and damper 
clamp installed.

Minimum Non-
Combustible 
Material 

Minimum Non-
Combustible 
Material Height 

Distances to 
Underside of
Mantel 

Top of Fireplace
Opening

Underside of
Mantel Shelf

12"

(A)

28"

34 

1

/

2

" 38 

5

/

8

" 42"

All minimum 
distances are
in inches

1

/

2

"

6"

8"

10"

Mantel Shelf

Minimum Non-
Combustible 
Material 

8"
Min.

14 

1

/

2

" 18 

5

/

8

" 22 

1

/

2

"

All minimum 
distances are
in inches

26"

1

/

2

"

6"

8"

10"

12"

Distances to 
Underside of
Mantel 

Hood
(GA6050, 
GA6052
or GA6053)

Top of Fireplace
Opening

Underside of
Mantel Shelf

IMPORTANT:

 If you cannot meet these minimum 

clearances, you must operate heater with chimney 

flue damper open. Go to 

Installing Damper Clamp 

Accessory for Vented Operation

, page 12.

Summary of Contents for CSM2618NR

Page 1: ...al switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire departmen...

Page 2: ...ce with ANSIZ21 11 2 Exception Donot install this appliance in a fac tory builtfireplacethatincludes instructions stating it has not been tested or should not be used with unvented gas logs WARNING Th...

Page 3: ...ns toblowdirectlyintothefireplace Avoidanydraftsthatalterburner flame patterns Ceiling fans can create drafts that alter burner flame patterns Altered burner patterns can cause sooting WARNING Do not...

Page 4: ...these products may create a white powder residue within the burner box or on adjacent walls and furniture 9 This heater needs fresh outside air ventilation to run properly this heater has an Oxygen De...

Page 5: ...in the Commonwealth of Massachusetts Product Features OPERATION This heater is clean burning It requires no outside venting There is no heat loss out a vent or up a chimney Heat is generated by both r...

Page 6: ...l Gas Code ANSI Z223 1 NFPA 54 defines a confined space as a space whose vol ume is less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kw of the aggregate input rating of all appliances install...

Page 7: ...hodsdescribed in the National Fuel Gas Code ANSIZ223 1 NFPA54Section5 3 or applicable local codes VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining un co...

Page 8: ...NING Seal any fresh air vents or ash clean out doors located on floor or wall of fire place If not drafting may cause pilot outage or sooting Use a heat resistant sealant Do not seal chimney flue damp...

Page 9: ...IREPLACE CLEARANCE TO COMBUSTIBLE MATERIALS SIDE WALL 16 CEILING 42 FLOOR 5 LOG SIZING REQUIREMENTS MINIMUM FIREBOX SIZE LOG SIZE HEIGHT DEPTH FRONT WIDTH REAR WIDTH 18 18 14 30 20 5 24 18 14 35 24 5...

Page 10: ...Figure 6 are not met you must have a hood When using a hood there are still certain minimum mantel clearances required Follow minimum clearances shown in Figure 7 when using hood Figure 6 Minimum Mant...

Page 11: ...ON Note When used as a vented decorative appliance must be installed only in a solid fuel burning fireplace with a working flue and constructed of noncombustible material For Massachusetts Residents O...

Page 12: ...s needed You must raise the fireplace floor to allow access to heater control panel This will insure adequate air flow and guard against sooting Raise fireplacefloorwithnoncombus tiblematerial Makesur...

Page 13: ...Tank External Regulator Figure 13 External Regulator With Vent Pointing Down Vent Pointing Down For propane LP units the installer must supply an external regulator The external regulator will reduce...

Page 14: ...pply piping system Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak 5 Correct all leaks at once 6 Reconnect heater and equipment shutoff valve to gas supply Check reco...

Page 15: ...ints Bubbles forming show a leak 5 Correct all leaks at once 6 Light heater see Operating Heater page 16 Check all other internal joints for leaks 7 Turn off heater Equipment Shutoff Valve Open Closed...

Page 16: ...lly within one minute when the switch is in the ON position after the pilot is lit 5 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B...

Page 17: ...Figure 15 page 15 MANUAL LIGHTING PROCEDURE 1 Follow steps 1 through 6 under Lighting Instructions page 16 2 Depress control knob and light pilot with match 3 Keep control knob pressed in for30 second...

Page 18: ...ime or as a child safety feature to prevent accidental ignition of the fireplace the receiver ON OFF REMOTE switch should be in the OFF position Auto Shutoff Feature 1 If the average room temperature...

Page 19: ...yellow color yellow decorative flames are visible as the flames exit the log set The base of the log set and the underside of the top logs glow red Natural gas models will burn with more blue flame wh...

Page 20: ...can please follow the directions on the can If you don t follow directions on the can you could damage the pilot assembly 1 Shut off the unit including the pilot Allow the unit to cool for at least t...

Page 21: ...pe Propane LP Only Ignition Piezo Manifold Pressure 10 6 3 W C Inlet Gas Pressure in of water Maximum 14 W C Minimum 11 W C For purpose of input adjustment Manufactured by DESA 1769 E Lawrence St Russ...

Page 22: ...ne LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tightennuthold...

Page 23: ...rol knob pressed in 30 seconds 3 Wait one minute for safety in terlock system to reset Repeat ignition operation 4 Fully open equipment shutoff valve 5 A Contact local natural or propane LP gas compan...

Page 24: ...2 Operate burners until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum instal lation clearances see pages 9 through 12 4 Clean burners see...

Page 25: ...logged 1 Gas leak See warning statement at top of page 2 Control valve or gas control defective 1 Foreign matter between con trol valve and burner 2 Gas leak See warning statement at top of page 1 Han...

Page 26: ...eater the replacement part number EQUIPMENT SHUTOFF VALVE GA5010 For all models Equipment shutoff valve with 1 8 NPT tap Fits 1 2 NPT pipe FIREPLACE HOOD Black GA6050 Brass GA6052 Antique Brass GA6053...

Page 27: ...r log pieces Control Cover Media Kit cc100 For all models This kit is used as an addition to or instead of the Floor Media Kit FM100 It includes 6 fiber log chunks to be placed on the fireplace floor...

Page 28: ...www desatech com 120163 01A 28 Illustrated Parts Breakdown Models CSM2618NR CSM2618PR CSM3624NR and CSM3624PR 1 4 5 3a 3b 6 9 11 2 12 13 16 18 8 19 22 7 10 20 17 14 15...

Page 29: ...pter 1 9 111804 01 Burner 1 111804 03 Burner 1 10 111819 04 Orifice 1 111819 05 Orifice 1 111819 14 Orifice 1 111819 15 Orifice 1 11 111807 01 Valve 1 111807 02 Valve 1 12 111796 01 Valve Bracket 1 13...

Page 30: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 31: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 32: ...odes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result...

Reviews: