DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
CDV37N/P AND CDV41N/P
Fireplace size
D x FW x RW
37"
18
1
/
2
"
37"
14"
41"
18
1
/
2
"
41"
18"
PRE-INSTALLATION
PREPARATION
LOCATION AND SPACE
REQUIREMENTS
Determine the safest and most efficient loca-
tion for your Comfort Glow direct-vent fire-
place. Make sure that rafters and wall studs
are not in the way of the venting system.
Choose a location where the heat output is
not affected by drafts, air conditioning ducts,
windows or doors. Figure 2 shows some
common locations. Read all venting infor-
mation in this manual. Be aware of all re-
strictions and precautions before deciding
the exact location for your fireplace.
When deciding the location of your fire-
place, follow these rules:
1.
Do not connect this fireplace to a chim-
ney flue serving a separate solid-fuel
burning fireplace or appliance.
2.
Due to high temperatures, do not lo-
cate this fireplace in high traffic areas
or near furniture or draperies.
3.
Proper clearances must be maintained.
4.
If your fireplace is to be installed di-
rectly on carpeting, vinyl tile, or any
combustible material other than wood,
it must be installed on a metal or wood
panel extending the full width and
depth of the fireplace. See Figure 3.
20"
34
3
/
4
"
5/8" for drywall facing
Must maintain a minimum
1" clearance to combustibles
37
1
/
2
"
41
1
/
2
"
34
3
/
4
"
20" Vertical Termination
19" Horizontal Termination
Note: Where two numbers are given the top number is exclusive to the
37" Fireplace and the bottom number is exclusive to the 41" Fireplace
CLEARANCES
Minimum clearances to combustibles for
the fireplace are as follows:
Back, and sides
0"/mm
Perpendicular walls
6" (152mm)
Floor
0"/mm
Ceiling to louver opening
42" (1067mm)
Front
36" (914mm)
Top of Standoffs
0"/mm
See General Venting on page 5 for specific
venting clearances.
FRAMING AND FINISHING
Figures 4 and 5 show typical framing of this
fireplace. Figure 6 on page 5 shows framing
for corner installation. All minimum clear-
ances must be met. Do not install fireplace
directly on carpeting, vinyl tile, or any com-
bustible material other than wood. The fire-
place must set on a metal or wood panel
extending the full width and depth of the
fireplace.
See Accessories on page 33 for mantel kits
available for this fireplace. If you are using
a separate combustible mantel piece, refer
to Figure 7 on page 5 for proper installation
height. You can install non-combustible
mantels at any height above the fireplace.
Figure 2 - Common Fireplace Locations
Figure 4 - Framing Clearances for Installation Against an Exterior Wall
Figure 5 - Framing Clearances for Typical
Fireplace Installation
Flush with a wall
Through exterior wall
enclosed in a chase
Corner
installation
Figure 3 - Fireplace Bottom Dimensions
D
RW
FW