Comfort Flame NCBurnerZMN Installation And Operation Instructions Manual Download Page 6

Comfortflame.US.com

900577-00_NC

6

AIR FOR COMBUSTION AND VENTILATION

  

Continued

4.  Compare the maximum Btu/Hr the space can support with the 

actual amount of Btu/Hr used.

   ______ Btu/Hr (maximum the space can support) 
   ______ Btu/Hr (actual amount of Btu/Hr used)
  Example: 51,200 Btu/Hr (maximum the space can support) 
   

70,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual 

Btu/Hr used is more than the maximum Btu/Hr the space can support. 

You must provide additional fresh air. Your options are as follows:

A.

  Rework worksheet, adding the space of an adjoining room. If the 

extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation 

Air From Inside Building.

B.

 Vent room directly to the outdoors. See Ventilation Air From 

Outdoors.

C.

  Install a lower Btu/Hr appliance, if lower Btu/Hr size makes room 

unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space 

can support, the space is an unconfined space. You will need no ad-

ditional fresh air ventilation.

 WARNING: If the area in which the appliance may 

be operated does not meet the required volume for 

indoor combustion air, combustion and ventilation air 

shall be provided by one of the methods described in 

the National Fuel Gas Code, ANSI Z223.1/NFPA 54, the 

International Fuel Gas Code, or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When 

ventilating to an adjoining unconfined space, you must provide two 

permanent openings: one within 12" of the ceiling and one within 

12" of the floor on the wall connecting the two spaces (see options 

1 and 2, Figure 2). You can also remove door into adjoining room 

(see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI 

Z223.1/NFPA 54, Air for Combustion and Ventilation for required size 

of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must 

provide two permanent openings: one within 12" of the ceiling and 

one within 12" of the floor. Connect these items directly to the out-

doors or spaces open to the outdoors. These spaces include attics 

and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/

NFPA 54, Air for Combustion and Ventilation for required size of 

ventilation grills or ducts.

IMPORTANT:

 Do not provide openings for inlet or outlet air into attic 

if attic has a thermostat-controlled power vent. Heated air entering 

the attic will activate the power vent.

Figure 3 - Ventilation Air from Outdoors (Stove Model Shown)

Figure 2 - Ventilation Air from Inside Building (Stove Model 

Shown)

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

Summary of Contents for NCBurnerZMN

Page 1: ...iance It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section on page 5 of...

Page 2: ...g DANGER Carbon monoxide poisoning may lead to death Carbon Monoxide Poisoning Early signs of carbon monoxide poi soning resemble the flu with headaches dizziness or nausea If you have these signs the...

Page 3: ...ood burning fireplace Use only model NCBurnerZMN P series vent free gas log appliance for Newcastle cast iron stove models 6 Do not add extra logs or ornaments such as pine cones vermiculite or rock w...

Page 4: ...allation in the US state of Massachusetts if the following additional requirements are met Un vented Room Heaters shall be installed in accordance with 527 CMR 30 Installation and repair must be done...

Page 5: ...al fresh air See Ventilation Air From Outdoors page 6 If your home does not meet all of the three criteria above proceed to Determining Fresh Air Flow For Fireplace Location Confined and Unconfined Sp...

Page 6: ...orapplicablelocalcodes VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to an adjoining unconfined space you must prov...

Page 7: ...ustion and Ventilation page 5 CHECK GAS TYPE Use only the correct type of gas natural or propane LP If your gas supply is not the correct gas type do not install appliance Call dealer where you purcha...

Page 8: ...r failure to use only parts specifically approved with this appliance may result in property damage or personal injury 1 Remove log from carton 2 Remove all protective packaging applied to log for shi...

Page 9: ...could occur Install external regulator with the vent pointing down as shown in Figure 9 Pointing the vent down protects it from freezing rain or sleet CAUTION Use only new black iron or steel pipe Int...

Page 10: ...1 2 PSIG 3 5 kPa 1 Disconnect appliance with its appliance main gas valve control valve and equipment shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage appliance...

Page 11: ...nts for leaks 7 Turn off appliance see To Turn Off Gas to Appliance page 13 Figure 12 Checking Gas Joints Stove Model Shown Control Valve Location Propane LP Supply Tank Equipment Shutoff Valve Figure...

Page 12: ...ear the floor If you smell gas STOP Follow B in the safety information If you don t smell gas go to the next step 6 Press in and turn control knob counterclockwise to the PILOT position Press in contr...

Page 13: ...and burner flame patterns often PILOT FLAME PATTERN Figure 19 shows a correct pilot flame pattern Figure 20 shows an incorrect pilot flame pattern The incorrect pilot flame is not heating the thermoco...

Page 14: ...the burner tube and pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Your local computer store hardware store or home center...

Page 15: ...gas pressure B Dirty or partially clogged ODS pilot 5 Thermocouple connection loose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect Igniter cable 2 Free Igniter cab...

Page 16: ...an burner see Cleaning and Mainte nance page 14 or replace burner orifice 1 Clean burner see Cleaning and Mainte nance page 14 or replace burner orifice 2 Replace damaged burner 3 Replace gas control...

Page 17: ...essure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at...

Page 18: ...plier TECHNICAL SERVICE You may have further questions about installation operation or troubleshooting Please contact your IHP dealer for any questions or concerns When contacting your dealer please h...

Page 19: ...urned on and off by using a hand held remote control ON OFF F1077 MRC Standard On Off Remote Control Kit RECEIVER AND ON OFF TOUCH SCREEN REMOTE CONTROL KIT For all Remote Ready Models Allows the burn...

Page 20: ...mfortflame US com 900577 00_NC 20 PARTS MODELS NCBURNERZMN AND NCBURNERZMP O F F P I L O T O N H I L O H I L O O F F P I L O T O N 17 17 18 19 24 15 14 16 13 12 12 11 22 23 20 10 9 21 4 8 5 3 2 21 7 6...

Page 21: ...3 1 11 J3808 LOWER BRACKET 1 12 J1958 SCREW HWH AB 8 18 X 38 7 13 PAINTED BASE ASSEMBLY 1 14 J3569 CABLE IGNITER 1 15 J3746 KIT IGNITER SERVICE 1 16 J3821 PLATE SWITCH 1 17 J3574 SCREW PPH AB 10 16 X...

Page 22: ...________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ __...

Page 23: ...el will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the i...

Page 24: ...r name P900577 00 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products...

Reviews: