SNMP
Using SNMP protocol you can read actual measured values, alarm status and alarm
parameters. Via SNMP protocol is also possible to get last 1000 measured values from history
table. Writing via SNMP protocol is not supported. It is supported
SNMPv1
protocol
version only. SNMP used
UDP port 161
. OID keys description can be found in the MIB
table, which can be obtained from device website or from your distributor. The password
for reading (SNMP read community) is factory set to
public
. The changes can be made using
TSensor software or web interface. OID keys:
OID
Description
Type
.1.3.6.1.4.1.22626.1.2.1
.1.3.6.1.4.1.22626.1.2.1.1.0
Actual measured temperature
String
.1.3.6.1.4.1.22626.1.2.1.2.0
Actual measured relative humidity
String
.1.3.6.1.4.1.22626.1.2.1.3.0
Actual measured computed quantity
String
.1.3.6.1.4.1.22626.1.2.1.4.0
Actual measured atmospheric pressure, CO
2
concentration
String
.1.3.6.1.4.1.22626.1.2.1.5.0
Temperature alarm state ("none", "high", "low")
String
.1.3.6.1.4.1.22626.1.2.1.6.0
Relative humidity alarm state
String
.1.3.6.1.4.1.22626.1.2.1.7.0
Computed quantity alarm state
String
.1.3.6.1.4.1.22626.1.2.1.8.0
Atmospheric pressure, CO
2
concentration alarm state
String
.1.3.6.1.4.1.22626.1.2.1.9.0
Temperature unit
String
.1.3.6.1.4.1.22626.1.2.1.10.0
Relative humidity unit
String
.1.3.6.1.4.1.22626.1.2.1.11.0
Computed quantity unit
String
.1.3.6.1.4.1.22626.1.2.1.12.0
Atmospheric pressure, CO
2
concentration unit
String
.1.3.6.1.4.1.22626.1.2.1.13.0
Min. temperature memory
String
.1.3.6.1.4.1.22626.1.2.1.14.0
Min. relative humidity memory
String
.1.3.6.1.4.1.22626.1.2.1.15.0
Min. computed value memory
String
.1.3.6.1.4.1.22626.1.2.1.16.0
Min. atmospheric pressure, CO
2
concentration memory
String
.1.3.6.1.4.1.22626.1.2.1.17.0
Max. temperature memory
String
.1.3.6.1.4.1.22626.1.2.1.18.0
Max. relative humidity memory
String
.1.3.6.1.4.1.22626.1.2.1.19.0
Max. computed value memory
String
.1.3.6.1.4.1.22626.1.2.1.20.0
Max. atmospheric pressure, CO
2
concentration memory
String
.1.3.6.1.4.1.22626.1.2.2
.1.3.6.1.4.1.22626.1.2.2.1.0
Device name
String
.1.3.6.1.4.1.22626.1.2.2.2.0
Device serial number
String
.1.3.6.1.4.1.22626.1.2.2.3.0
Device type
String
.1.3.6.1.4.1.22626.1.2.3
.1.3.6.1.4.1.22626.1.2.3.1.0
Actual measured temperature
Int*10
.1.3.6.1.4.1.22626.1.2.3.2.0
Actual measured relative humidity
Int*10
.1.3.6.1.4.1.22626.1.2.3.3.0
Actual measured computed quantity
Int*10
.1.3.6.1.4.1.22626.1.2.3.4.0
Actual measured atmospheric pressure, CO
2
concentration
Int*X
.1.3.6.1.4.1.22626.1.2.3.5.0
Temperature alarm (0
–
none, 1
–
high, 2
–
low)
Integer
.1.3.6.1.4.1.22626.1.2.3.6.0
Relative humidity alarm state
Integer
.1.3.6.1.4.1.22626.1.2.3.7.0
Computed quantity alarm state
Integer
.1.3.6.1.4.1.22626.1.2.3.8.0
Atmospheric pressure, CO
2
concentration alarm state
Integer
.1.3.6.1.4.1.22626.1.2.4
.1.3.6.1.4.1.22626.1.2.4.1.0
Temperature low limit
Int*10
.1.3.6.1.4.1.22626.1.2.4.2.0
Temperature high limit
Int*10
.1.3.6.1.4.1.22626.1.2.4.3.0
Relative humidity low limit
Int*10
.1.3.6.1.4.1.22626.1.2.4.4.0
Relative humidity high limit
Int*10
.1.3.6.1.4.1.22626.1.2.4.5.0
Computed quantity low limit
Int*10
.1.3.6.1.4.1.22626.1.2.4.6.0
Computed quantity high limit
Int*10
.1.3.6.1.4.1.22626.1.2.4.7.0
Temperature time-delay
Integer