ANTENNA MONITORING SYSTEM (AMS) USER MANUAL
ENU STATUS: 1-0-0
Copyright - refer to title page
Page 32
180 or 300 seconds with 3 or 2 cycles respectively, is generally acceptable for AHJ inspections. If
there are no false alarms at the default settings, this is most recommended for testing and post
inspection.
o
Maximum Cycle length of 250 with 5 min periods is 20.8 hrs before first alarm will appear at
FACP.
Figure 18: Commissioning Procedure – Poll Editing
Step 6
: Slide “Status” bar green under “Polling” to engage auto mode. All other settings and tabs will be
locked during this mode.
Step 7:
Close OMT software. Keeping software open while AMS is in auto mode for extended periods
causes software to freeze. To resolve, see section: Commissioning Troubleshooting Steps.
End of Section