InteliVision 13Touch Global Guide
17
Note:
Ethernet connection is available for all controllers mentioned in chapter related products via
InternetBridge-NT (See the chapter Multiple Ethernet connection). You can also use InternetBridge-NT without
the need for a public IP address (find details on our AirGate technology on our website
)
Using a web browser
An Ethernet connection to the controller allows one to use any web browser for basic monitoring and
configuration. Simply enter the IP address of the module into the address bar of your web browser, e.g.
http://192.168.1.254
and then enter the access code. When connecting through a web browser,
there is 5-minute timeout period after closing the browser window. After that, the client is automatically
logged out.
Ethernet connection settings
Settings can be edited via any type of connection (USB or Ethernet). Setup is provided via InteliMonitor.
For the Ethernet connection, set the following options in the Comms Settings group:
Image 5.2 Controller IP settings
Note:
The IP addresses of the controllers must be accessible from the IV13T. If the IV13T is connected to
another LAN segment than the gen-sets are, there must be a gateway (router) that enables direct traffic
between the segments. If the IV13T is connected via the Internet, then the internet gateway of the LAN where
the gen-sets are connected must have a public IP address, must allow incoming traffic and must provide port
forwarding from the external public IP address to the various internal gen-set IPs according to the port used.
5.1.2 USB connection
IMPORTANT: USB ports are not suitable to be used for monitoring purposes. USB ports should be
used for configuration only. This recommendation is valid not only for InteliVision 13Touch, it is
valid in general. When using InteliVision 13Touch for monitoring, its Ethernet ports should be
used.