InteliVision 13Touch Global Guide
18
Image 5.3 Point to point USB connection
IV13T settings
Controller settings
2 x USB 2.0 serial ports
2 x USB 3.0 serial ports
No special settings required
No special settings required.
Some controllers only via ext. bridge.
Table 5.2 Communication settings for the IV13T and controller
Note:
Direct USB connection is not possible for some controllers. However, USB connection is available for all
above-mentioned controllers via InternetBridge-NT
5.2 InteliVision 13Touch connection to a Multiple
gen-set
5.2.1 Multiple Ethernet Connection
Even though the software allows to configure up to 32 controllers
the hardware is designed for simultaneous
monitoring and control of up to 4 controllers only.
Many different kinds of Ethernet topology exist. The
basic point to point Ethernet connection can be made by a direct or cross Ethernet cable. In addition it is also
possible to monitor more than one controller in a site through a switch (TCP/IP protocol-based network).
Another possibility is establishing a connection through the internet network, but for this a public IP address is
necessary (or AirGate ComAp technology, see our website
for more information). The
physical configuration of such a network can be a small Ethernet LAN or also over the internet.