InteliLite Global Guide
120
Image 5.31 Engine stops after first
Electric state machine
IslOper
Island operation
BrksOff
GCB opened
5.5.19 Sensor curves
Background of the sensor calibration
To correct measuring error of each analog input (pressure, temperature, level, etc.) calibrating constants should
be set. Calibration is made by adding the value of setpoint
CU AIN1 Calibration (page 327)
, or
, or
CU AIN3 Calibration (page 328)
, or
CU AIN4 Calibration (page 329)
directly to
the calculated value at analog input.
Note:
The calibration must be done at the operational point of the analog input (e.g. 80°C, 4.0Bar etc..)
Default sensor curves
There are 16 default resistive curves available. The following table provides information on minimum/maximum
values of respective sensors. Actual values especially of temperature curves may differ. Meaning is to prolong
curve to the lower temperature values, so the cold engine will not raise alarm fail sensor.
Curve
Min [Ohm]
Max [Ohm]
Units
VDO 10 Bar 0-2400ohm
0
2400
Bar
VDO40-120°C0-2400ohm
0
2400
°C
VDOLevel%0-2400ohm
0
2400
%
General line 1
0
1000
ohm
General line 2
0
1000
ohm
General line 3
0
1000
ohm
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...