InteliLite4 AMF20 Global Guide
489
LBO: L
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
51
Description
Particular instances of the load shedding functionality
The load shedding outputs are activated (load is being shedd) in the order 1, 2, 3, 4, 5.
The load shedding outputs are deactivated (load is being reconnected) in the order 5, 4, 3, 2, 1.
The load disconnected by the LBO Nr.1 is the less essential load of these three possible loads instances.
Load Shedding Stage 1
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
52
Description
Particular instances of the load shedding functionality
The load shedding outputs are activated (load is being shedd) in the order 1, 2, 3, 4, 5.
The load shedding outputs are deactivated (load is being reconnected) in the order 5, 4, 3, 2, 1.
The load disconnected by the LBO Nr.1 is the less essential load of these three possible loads instances.
Load Shedding Stage 2
back to Logical binary outputs alphabetically
LBO: M
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
78
Description
This output is active while mains failure is not detected and mains voltage and frequency is within limits.
Mains Healthy is active when mains f and V are within the protection limits
Mains Healthy deactivates when there is active mains protection level 2
Mains Healthy cannot be activated when there is inactive not confirmed alarm
in the alarmlist
Note:
Mains Healthy cannot be activated when there is active
ALI Mains Ph Rotation Opposite
or
ALI Mains Ph L1 Inverted (page 549)
ALI Mains Ph L2 Inverted (page 549)
or
Mains Ph L3 Inverted (page 549)
.
Mains Healthy