559
Alarm Type
SD
Alarmlist message
EM(A) - missing or damaged
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that there is a problem with communication with module in
slot (in first 5 second there was no communication and module is configured in
slot).
Sd EM(A) - missing or damaged
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
EM(B) - missing or damaged
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that there is a problem with communication with module in
slot (if first 5 second there was no communication and module is configured in
slot).
Sd EM(B) - missing or damaged
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd ECU Communication Fail
Alarm evaluated
With configured LBO
– only when this LBO is
active
Without configured LBO
– all the time
Related applications
AMF, MRS
Description
This alarm occurs when an ECU is configured, but the communication with the
ECU is not established or has dropped out.
Sd ECU Communication Fail
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Emergency Stop
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
Alarm is activated when binary input
is activated.
The Gen-set shuts down in the moment the input is activated and starting is
blocked until the input is deactivated and fault reset is pressed.
Note:
Use red emergency button placed on the switchboard door and
connect it to a binary input of the controller. Then configure the function
Emergency Stop to this binary input. It is recommended to use NC contact of
the button.
Sd Emergency Stop