InteliLite4 AMF20 Global Guide
248
Coolant Temp BOC
Setpoint group
User Setpoints
Related FW
1.3.0
Range [units]
-16 .. 120 [°C]
Default value
90 °C
Alternative config
NO
Step
1 °C
Comm object
65530
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for
user protection.
Coolant Temp Low Delay
Setpoint group
User Setpoints
Related FW
1.3.0
Range [units]
0.0 .. 3600.0 [s]
Default value
0.0 s
Alternative config
NO
Step
0.1 s
Comm object
65529
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Delay for
Wrn Coolant Temp Low (page 536)
user protection.
Coolant Temp Low Wrn
Setpoint group
User Setpoints
Related FW
1.3.0
Range [units]
-16 .. 120 [°C]
Default value
5 °C
Alternative config
NO
Step
1 °C
Comm object
65528
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for
Wrn Coolant Temp Low (page 536)
user protection.